CFD-guided design and optimization of an off-grid solar-powered refrigerator for fruit and vegetable storage in rural Sub-Saharan Africa

  • Vicent Marwa

    Roles Conceptualization, Data curation, Formal analysis, Funding acquisition, Investigation, Methodology, Project administration, Resources, Software, Supervision, Validation, Visualization, Writing – original draft, Writing – review & editing

    vmarwa2000@gmail.com

    Affiliation Department of Mechanical and Industrial Engineering, Mbeya University of Science and Technology, Mbeya, Tanzania

    ⨯

Abstract

Methods

A 50 L cabinet for 10 kg of mixed produce was designed for stand-alone rural operation from a 200 Wp photovoltaic (PV) module, an MPPT controller and a 0.8 kWh LiFePO4 battery. The hardware uses an R134a DC vapor-compression circuit, 40 mm polyurethane insulation, a 1.5 mm galvanized outer shell, a 1.0 mm aluminium liner, a rear microchannel evaporator, a perforated supply plenum, an electronically commutated fan and 1 kg of 5 °C phase-change material (PCM). Thermal performance was obtained from a fully specified three-dimensional ANSYS Fluent model that solves the transient Reynolds-averaged Navier–Stokes equations with Boussinesq buoyancy and the SST k–ω closure, Darcy–Forchheimer resistance in the produce stacks, conjugate energy equations for air, walls and produce, and an enthalpy–porosity PCM formulation, loosely coupled to an R134a compressor map and a PV/battery balance. Five discrete design cases (C0–C4) were ranked by a constrained multi-objective criterion on pull-down time, air-temperature spread ΔT, daily electrical energy E_d, cycle COP, useful-zone velocity and passive holdover, subject to explicit bounds on setpoint, energy, cost, fan speed, PV size and local manufacturability.

Data

Relative to the unmanaged baseline cabinet, the selected configuration C4 reduced the cyclic air-temperature spread from 6.4 °C to 2.0 °C, shortened 10 kg pull-down from 3.6 h to 2.5 h, and lowered predicted daily energy at 35 °C from 0.68 to 0.51 kWh day-1 (COP = 1.62). At 43 °C ambient the same cabinet remained at 0.74 kWh day-1. The PCM pack provided 4.0 h of passive holdover after a power cut. A conventional grid-powered 50 L compact refrigerator serving the same 10 kg load with twelve 30 s door openings at 35 °C is estimated, from published compact-appliance ratings derated to tropical duty, to consume 0.90–1.10 kWh day-1. C4 therefore uses 43–54% less electricity than that conventional baseline, or 143–215 kWh year-1, without drawing any grid energy. Refrigerator hardware is costed at approximately USD 294 and the complete off-grid kit at USD 569. Mesh M3 (0.98 × 106 cells) has a fine-grid GCI of 0.8% on mean air temperature; the domain heat-balance error is 0.7%.

Conclusion

The first-order design lever is cabinet airflow management, not compressor oversizing: the plenum accounts for most of the uniformity and pull-down gain, while the PCM is a resilience lever that trades 0.2 h of pull-down for 4.0 h of holdover. The resulting appliance is locally fabricable, but R134a charging and recovery must be performed only by a trained refrigeration technician. Commodity-specific setpoints and prototype validation against the defined outputs remain prerequisites for field deployment.

Introduction

Fresh fruit and vegetables are central to nutrition and income generation in Sub-Saharan Africa, but they are among the most temperature-sensitive commodities in agricultural value chains. Reviews of cold-storage and postharvest practices report that fruit and vegetable losses in the region are commonly 30–50%, with particularly high losses in rural first-mile handling, where grid electricity, refrigeration, and pre-cooling are absent [1–4]. Food-loss reduction is also an energy and environmental problem: without suitable storage, embedded land, water, fertilizer and transport energy are lost before food reaches consumers [5]. Previous work has therefore emphasized low-cost postharvest technologies, improved packaging, pre-cooling, cold rooms and renewable-powered cooling as complementary interventions [6–8].

Conventional vapor-compression refrigerators are efficient and familiar to technicians, yet many appliances sold into hot climates are not optimized for produce loads, intermittent power, high door-opening frequency or local repair. Poor internal airflow can create cold spots that chill sensitive produce and hot spots that accelerate respiration. Oversized fans improve mixing but can increase dehydration and energy consumption. Conversely, insufficient fan flow causes stratification and slow pull-down. The environmental benefit of cooling is also reduced when high-GWP refrigerants or inefficient insulation are used [9].

Computational fluid dynamics is the appropriate analysis tool for this class of appliance because the design question is spatial, not merely capacity-based. A compressor sized to the 24 h mean load can still leave a lower-front crate above the chilling limit if the evaporator jet short-circuits; conversely, an oversized fan can meet a mean-temperature target while dehydrating leafy vegetables. Cabinet-scale CFD resolves that competition. The established modelling route for packed produce is a porous-media representation of ventilated crates, in which Darcy–Forchheimer resistance replaces fruit-resolved geometry and a local-thermal-equilibrium energy equation carries the bulk heat capacity of the load [10]. Agyeman et al. used that approach to redesign tomato crates and showed that vent area and airflow path control cooling time more strongly than the nominal refrigeration capacity [11]. Alexander et al. optimized a large apple cold store and reduced temperature heterogeneity by rearranging bins and supply openings, again without changing the plant [12]. Khalid and Ahsan illustrated the same RANS machinery on an internal compressible flow and confirmed that a two-equation closure is sufficient when the quantity of interest is a pressure drop and a mean thermal field rather than a resolved turbulence spectrum [13]. What those studies do not provide is a closed design loop from a 50 L, locally welded cabinet, through a produce-aware CFD model, to an off-grid PV/battery and PCM specification that a rural workshop can build.

Recent work on renewable-assisted cold thermal energy storage (CTES) and hybrid solar cooling supplies the complementary energy-system context. Alam et al. reviewed renewable-assisted CTES air-conditioning and showed that coupling solar, wind or geothermal sources to PCM or ice storage can cut greenhouse-gas emissions by more than 75% relative to conventional plant, provided that intermittency (typically a 10–15% performance swing) is absorbed by storage and intelligent control [14]. Irshad et al. demonstrated experimentally that an RT-18 HC PCM cold store raised the cooling capacity of a compact air-cooling circuit by 35.8% and produced a daily COP of 1.67 at an optimal refrigerant flow of 0.70 kg min-1 [15]. Mukhtar et al. reviewed nano-enhanced PCMs for buildings and documented 20–30% gains in effective conductivity with carbon-based nanoparticles, together with a clear warning that long-term stability and cost still limit field use [16]. Zaki et al. showed that boosted ensemble regression trees can predict HVAC energy and environmental performance in office buildings with high fidelity and thereby expose saving strategies for air-conditioning and lighting [17]. These four contributions are important, and they are used below, but they address building air-conditioning, not first-mile horticultural refrigeration in a no-grid SSA market. The present appliance borrows their PCM-holdover and solar-storage logic and relocates it to a 50 L produce cabinet whose figure of merit is commodity temperature uniformity, not indoor comfort.

A structured comparison with the closest published configurations is given in Table 13 (placed with the results so that the numerical values of this study can be read against it). Three gaps remain in that literature. First, produce-CFD studies stop at the crate or the cold room and do not close on a manufacturable off-grid bill of materials. Second, solar-refrigerator and CTES studies treat the cabinet as a well-mixed box and therefore cannot see the lower-front hot spot that dominates first-mile quality loss. Third, almost none state the optimization problem decision variables, objective weights, inequality constraints and allowable parameter ranges against which the ‘optimized’ design was selected. The present paper is written to close those three gaps.

Novelty, distinctiveness and the authors’ position

This is not a cogeneration plant and is not offered as one. It is a first-mile, off-grid produce refrigerator. Its distinctiveness, relative to a basic vapor-compression box or a building-scale solar-CTES system, lies in five contributions that are the authors’ own analysis rather than a re-description of known hardware:

  1. i. A cabinet-scale, fully written CFD model that treats the produce as a Darcy–Forchheimer porous load, the envelope as a conjugate three-layer solid, and the PCM as an enthalpy–porosity continuum, then loosely couples those fluxes to an R134a compressor map and a PV/battery balance. The equation set, output definitions and heat-balance check are given in Section 2 so that the design numbers can be reconstructed.
  2. ii. A discrete, constrained multi-objective optimization (Section 2.11) whose criteria are produce-specific (ΔT, pull-down, holdover, dehydration-safe velocity) rather than a single COP or a comfort temperature. The constraints, decision variables and allowable ranges are stated explicitly.
  3. iii. A commodity-aware operating policy (Table 1) that refuses the fiction of a universal 5 °C box for tropical fruit, and a service model that separates sheet-metal fabrication from certified R134a handling.
  4. iv. A quantitative reading of current techniques (Section 5.1): airflow management is shown to be the first-order lever, PCM the resilience lever, and insulation the ambient-robustness lever. That ranking is the authors’ interpretation of the C0–C4 increments, not a restatement of manufacturer claims.
  5. v. A forward perspective (Section 6) on how this class of appliance should evolve: low-GWP drop-in with charge limits, nano-enhanced 5 °C PCM only after cost and cycling are proven, cooperative shared-use CTES, and a field digital twin in the spirit of Zaki et al. [17] once prototype data exist.

The objective of this study is therefore to design and numerically evaluate an off-grid solar-powered, low-energy refrigerator for short-term storage of vegetables and selected fruits under SSA boundary conditions. Specific aims are to: (i) define commodity-aware thermal and energy requirements; (ii) develop a Fluent CFD model of airflow and heat transfer in a 50 L produce refrigerator, with every conservation equation, closure, boundary condition and output metric stated explicitly; (iii) pose and solve a constrained discrete optimization on insulation, plenum/baffle design, fan flow, PCM holdover and PV arrangement; (iv) validate the model statistically against mesh refinement, energy closure and published analogues; and (v) propose a manufacturing route, trained-technician service model and bill of materials for local fabrication. Prototype measurements remain a required next step before commercial deployment; they are specified against the same outputs used to rank the designs.

Materials and methods

Commodity requirements and design context

The appliance targets first-mile storage at farms, aggregation centers, kiosks and urban markets where ambient temperatures can exceed 35 °C and no grid electricity is available. Because fruit and vegetables have different chilling limits, the refrigerator is designed as an adjustable-temperature appliance rather than a universal 5 °C box. The 5–8 °C mode is intended for leafy vegetables, citrus and short-term holding of compatible produce; warm operation at 8–12 °C is recommended for chilling-sensitive tropical fruits. Table 1 summarizes commodity guidance, and Table 2 lists engineering requirements that become the boundary conditions and acceptance targets of the numerical model.

thumbnail
Table 1. Commodity temperature guidance for using the proposed refrigerator.

https://doi.org/10.1371/journal.pone.0363334.t001

thumbnail
Table 2. Refrigerator design requirements and boundary conditions.

https://doi.org/10.1371/journal.pone.0363334.t002

Refrigerator concept and manufacturable layout

The proposed cabinet has an approximate external size of 0.45 m × 0.38 m × 0.60 m and a net refrigerated volume of 50 L. The cabinet uses a 1.5 mm galvanized steel outer shell, 40 mm polyurethane (PU) foam insulation, a 1.0 mm aluminium inner liner, a replaceable magnetic gasket and three removable shelves that accept vented crates. Cooling is supplied by an R134a DC compressor, air-cooled condenser, capillary tube, filter drier and rear microchannel evaporator. Electrical power is supplied only by the dedicated PV-battery subsystem; no grid connection is assumed. An electronically commutated (EC) fan supplies cold air to a perforated plenum at the top and rear of the chamber; return air flows through a lower rear gap. One 1 kg PCM pack melting at 5 °C is placed below the lowest crate to stabilize cycling and provide holdover during power cuts. The refrigeration skid is modular, allowing certified technicians to service it without replacing the cabinet. Fig 1 illustrates the concept and the extent of the CFD domain. Airflow arrows, refrigerant lines and the PV–battery chain are separated so that no traces overlap. The CFD domain comprises the cabinet air, conjugate wall layers, evaporator surface, perforated plenum, porous produce zones and PCM tray.

thumbnail
Fig 1. Off-grid solar-powered 50 L refrigerator concept, showing the insulated cabinet, internal plenum, evaporator/fan module, PCM tray, DC compressor and mandatory PV/battery subsystem.

https://doi.org/10.1371/journal.pone.0363334.g001

Computational domain and physical assumptions

The three-dimensional CFD domain (Fig. A.1) comprises: (i) the internal air volume; (ii) three porous produce zones representing vented crates on the shelves; (iii) the perforated supply plenum and rear return gap; (iv) the evaporator panel treated as a no-slip cooled wall; (v) the PCM tray; (vi) the three-layer cabinet envelope (galvanized steel / PU foam / aluminium); and (vii) a thin gasket leakage slot at the door perimeter. The compressor, condenser and capillary tube are excluded from the CFD domain and are represented only in the coupled system energy model of Section 2.8, because their influence on the cabinet appears as an evaporator thermal boundary condition and an electrical power draw. The following modelling assumptions are adopted and are used consistently in every case C0–C4:

  1. i. Air is Newtonian, incompressible and treated as a Boussinesq fluid. Density variations are retained only in the gravitational body-force term (Section 2.5.2). Reference properties are evaluated at 35 °C (Table 3).
  2. ii. Flow is three-dimensional, unsteady and turbulent in the free cabinet volume. The SST k–ω Reynolds-averaged Navier–Stokes (RANS) closure is used [13,18]. Laminar patches that arise in the deep crate cores are admitted by the low-Reynolds near-wall formulation.
  3. iii. Produce is not resolved fruit-by-fruit. Each crate is a homogeneous anisotropic porous zone with prescribed porosity, viscous resistance, inertial resistance and effective heat capacity (Section 2.5.4). This is the appropriate level of description for cabinet-scale airflow distribution and bulk pull-down [10–12].
  4. iv. Local thermal equilibrium (LTE) is assumed between interstitial air and produce within each porous zone. The single-energy-equation form is justified by the long thermal time scale of the 10 kg load (hours) relative to the interstitial convection time scale (seconds).
  5. v. Respiration is a weak volumetric heat source that depends on local produce temperature. Moisture loss, evaporation, frost growth, condensate films and quality kinetics are not solved; predicted temperatures are therefore engineering thermal performance, not shelf-life.
  6. vi. The PCM is an enthalpy–porosity continuum with a narrow mushy interval about 5 °C (Section 2.5.6). Natural convection inside the PCM pack is suppressed by the high mushy-zone source once the solid fraction is non-zero.
  7. vii. Door openings are not meshed as moving boundaries. Their thermal effect is imposed in the system energy model as a pulsed infiltration load (Section 3.2). A continuous gasket leakage path is retained in the CFD geometry.
  8. viii. Radiation inside the cabinet is neglected. Temperature differences among internal surfaces at steady cycling are of order 2–6 K, so the radiative flux is small compared with forced convection from the plenum jets.

Thermophysical properties

Thermophysical values used in the simulations are listed in Table 3. Air properties are constant except for the Boussinesq term. Solid-layer properties are those of the specified manufacturable wall. Produce bulk properties represent a mixed leafy-vegetable / hardy-fruit load at the 10 kg design mass. PCM sensible properties are typical of a commercial 5 °C organic pack and are required to close the enthalpy–porosity model; they were not reported in the original draft and are stated here as modelling assumptions.

thumbnail
Table 3. Thermophysical properties and model assumptions used in every simulation.

https://doi.org/10.1371/journal.pone.0363334.t003

Adopted CFD model and governing equations

ANSYS Fluent 2023 R1 was used as a pressure-based, transient, implicit solver [19]. The complete equation set actually discretized in the study is written below. The original draft quoted only the steady convective form of continuity, momentum and energy; that form is inconsistent with the transient solver, the PCM phase-change problem and the pull-down metric, and is replaced here by the unsteady statements that were solved.

Continuity and momentum in the free air volume.

Mass and momentum conservation for the incompressible cabinet air are

(1)(2)

where uᵢ is the Reynolds-averaged velocity, p is the modified pressure, μ is the molecular viscosity, μt is the turbulent eddy viscosity, gi is gravitational acceleration (g = −9.81 m s-2 in the vertical direction), Si is the porous resistance (zero outside produce zones) and Sβ,i is the Boussinesq buoyancy source. Repeated indices imply summation.

Buoyancy closure.

Density is written ρ = ρ0 [1 − β (T − T0)], and only the temperature-dependent part is retained as a body force. With the hydrostatic contribution of ρ0 gi absorbed into p, the buoyancy source is

(3)

The reference temperature is T0 = 6 °C (the nominal cabinet setpoint) and β = 1/T0, abs ≈ 3.25 × 10-3 K-1. Equation (3) is essential during compressor-off periods and in the lower-front corner, where forced convection is weak and residual stratification is buoyancy-driven. Gravity was enabled in every run.

Turbulence closure: SST k–ω.

The shear-stress transport (SST) k–ω model of Menter [18] was selected because the cabinet flow contains both a wall-bounded evaporator jet and large recirculation zones with adverse pressure gradients. The transported turbulent kinetic energy k and specific dissipation rate ω satisfy

(4)(5)

with the SST blending function F1, the eddy viscosity μt = ρ a1 k / max (a1 ω, Ω F2), and the standard Menter constants (a1 = 0.31, β* = 0.09) [18,19]. Enhanced wall treatment was used. Inflation layers were grown on the evaporator, plenum slots and inner liner so that the first-cell dimensionless wall distance satisfied y+ ≤ 5 on the evaporator and plenum lips and y+ ≤ 30 on the remaining cabinet walls. This resolution is required if the evaporator heat flux—and therefore every energy-related output—is to be grid-independent.

Porous produce stacks (Darcy–Forchheimer).

Inside each crate the momentum equation is augmented by the Darcy–Forchheimer sink, written in the superficial-velocity formulation used by Fluent [19]:

(6)

The first term is viscous (Darcy) drag and the second is inertial (Forchheimer) drag. The coefficients were not taken from a raw Ergun fit to individual fruit, which would overstate resistance for vented plastic crates. They were calibrated to the published pressure-drop range for ventilated horticultural packaging [10,11], giving 1/α = 1.8 × 106 m-2 and C2 = 85 m-1 at porosity ε = 0.42. Continuity is still given by Eq. (1); the solver uses superficial velocity to ensure mass is conserved across the porous/fluid interface. Effective conductivity of the stack is the volume-weighted mixture

(7)

which matches the value imposed in Table 3. The corresponding effective volumetric heat capacity used in the energy equation is

(8)

Equation (8) is the reason the 10 kg load dominates the thermal inertia of the cabinet and therefore sets the pull-down time scale derived in Section 3.4.

Energy equations for air, produce and walls.

A single static-temperature energy equation is solved in the air and, under the LTE assumption, in the porous produce zones:

(9)

where (ρ cp)* = ρ0 cp and k* = k_f in clear air, while (ρ cp)* = (ρ cp)_eff and k* = k_eff inside produce zones. The turbulent conductivity is kt = cp μt / Prt with Prt = 0.85. The volumetric source is

(10)

S_fan is applied only in the fan-volume cells as the dissipated electrical fan power (2.5–3.5 W). S_PCM is active only inside the PCM tray (Section 2.5.6). Respiration in the produce zones is

(11)

with q̇_resp (T6) = 0.015 W kg-1. At the 10 kg design load this source is only 0.15 W at 6 °C and about 0.3 W at 16 °C, so it does not control pull-down, but it is retained because it is the only continuous internal generation term once field heat has been removed.

Conjugate conduction is solved in every solid layer of the envelope and in the shelves:

(12)

Temperature and heat flux are continuous at fluid–solid interfaces. This conjugate treatment is used for the production mesh of cases C1–C4. The exploratory envelope study (part of C0/C1) was also run with an equivalent-U wall boundary, Eq. (31), to confirm that the two envelope representations agree to within 0.2 K on mean air temperature.

PCM enthalpy–porosity model.

The 1 kg PCM pack is modelled with the enthalpy–porosity method of Voller and Prakash [20]. The total enthalpy is split into sensible and latent parts,

(13)

where L = 180 kJ kg-1 is the latent heat and γ is the liquid fraction, linearized across a 1 K mushy interval centred on the nominal 5 °C melt temperature:

(14)

with T_s = 4.5 °C and T_ℓ = 5.5 °C. The energy equation in the PCM zone is Eq. (9) written in enthalpy form, which is equivalent to treating the latent contribution as the source

(15)

A Carman–Kozeny momentum sink freezes residual velocity as the pack solidifies,

(16)

with A_mush = 105 kg m-3 s-1 and ξ = 10-3. Equations (13)–(16) are the reason C4 is slightly slower to pull down than C3 (latent heat competes with produce cooling near 5 °C) and the reason C4 alone achieves a multi-hour holdover after power loss (latent heat is released back to the cabinet).

Boundary conditions, initial conditions and fan model.

All boundary conditions are stated mathematically so that the model can be reproduced.

Evaporator surface. During pull-down the microchannel evaporator is a no-slip isothermal wall

(17)

The −2 °C value is the saturation temperature consistent with the selected R134a capacity band (85–110 W at T_evap ≈ −2 °C, T_cond ≈ 45–55 °C). During daily-energy simulations the same surface is switched by the thermostat law of Section 2.8: Eq. (17) is applied while the compressor is ON, and an adiabatic wall (q_w = 0) is applied while it is OFF. The evaporator heat transfer rate extracted from the CFD solution is the surface integral

(18)

Fan. The EC fan is a lumped pressure-jump interior face. The quadratic curve

(19)

was fitted so that the operating point of the optimized cabinet (evaporator-to-return pressure drop ≈ 18 Pa on mesh M3) occurs at the design mass flow ṁ = 0.020 kg s-1. Fan electrical power is 2.5 W in C0–C2 and 3.5 W in C3–C4; the corresponding heat is deposited as S_fan.

External envelope. On the outer galvanized surface a mixed (convection) condition is imposed,

(20)

with T_amb ∈ {30, 35, 40, 43} °C according to the case. The value h_ext = 7 W m-2 K-1 represents natural convection on a shaded outdoor cabinet and is conservative relative to a wind-exposed surface. The door gasket leakage slot is a high-resistance porous strip connecting cabinet air to a far-field pressure opening at T_amb; its permeability is reduced from C0 to C4 to represent the low-leakage seal.

Initial conditions. Two initial states are used, corresponding to the two classes of output.

Pull-down (Section 2.7): the empty cabinet is first brought to a cyclic steady state at the 6 °C setpoint. At t = 0 the 10 kg produce zones are reset to a uniform field temperature T_p(x,0) = 31 °C and the PCM liquid fraction is set to γ(x,0) = 1 (fully liquid at 8 °C). This is the conservative first-loading condition after a warm start of the PCM pack. Holdover: starting from the cyclic steady state of C4 (PCM essentially solid, γ ≈ 0, produce at ~6 °C), the evaporator is switched to adiabatic and the fan is turned off at t = 0.

Discretization, time marching and convergence.

Spatial discretization is second-order upwind for momentum, k, ω and energy, with a second-order pressure interpolation. Pressure–velocity coupling uses the SIMPLE algorithm. Gradients are least-squares cell-based. The transient scheme is first-order implicit with a fixed time step Δt = 5 s. This step is small relative to the produce thermal time scale (τ_p ≈ 0.7–1.1 h, Section 3.4) and was verified by repeating the C4 pull-down at Δt = 2 s; the 8 °C crossing time changed by less than 1%. Under-relaxation factors were 0.7 (momentum), 0.8 (k, ω) and 0.95 (energy). A time step was accepted when residuals fell below 10-5 for continuity, momentum and turbulence and below 10 ⁻ ⁷ for energy, and when the instantaneous domain heat-balance error

(21)

remained below 1.5%. Here E_th is the instantaneous thermal energy stored in air, walls, produce and PCM. Equation (21) is the numerical integrity check on every energy-related output reported in Section 4. Pull-down runs covered 8 h of physical time; daily-energy runs covered 24 h after a 4 h cyclic start-up that was discarded. Solver settings are summarized in Table 4.

thumbnail
Table 4. Complete CFD setup implemented in ANSYS Fluent and used for all reported cases.

https://doi.org/10.1371/journal.pone.0363334.t004

Mesh, independence and numerical uncertainty

Four unstructured hybrid meshes (tetrahedral/polyhedral core, five prism inflation layers on the evaporator, plenum slots and inner liner) were generated. Local refinement was applied at the plenum perforations, evaporator leading edge, shelf gaps and porous interfaces (Fig. A.2). Mesh-quality histograms for the selected grid are given in Fig. A.3: maximum skewness 0.84 and minimum orthogonal quality 0.18, both inside accepted Fluent limits. Table 5 reports the four grids and the two monitored quantities volume-weighted mean air temperature T̄_air and evaporator-to-return pressure drop Δp. The narrative in the original draft (0.42–2.04 million cells; selected mesh 1.31 million) was inconsistent with Table 5 and Fig 2; the values in Table 5 are correct and are used throughout this revision. Mesh M3 (0.98 million cells) is the production grid.

thumbnail
Table 5. Mesh-independence results for the optimized C4 configuration at 35 °C ambient, cyclic steady state.

https://doi.org/10.1371/journal.pone.0363334.t005

thumbnail
Fig 2. Grid independence of the optimized C4 cabinet.

The two monitored quantities are plotted on separate axes with a single legend so that traces and labels do not overlap.

https://doi.org/10.1371/journal.pone.0363334.g002

M3 (0.98 million cells) is the production mesh: further refinement to M4 changes mean air temperature by 0.04 K (0.65%) and pressure drop by 0.2 Pa. The fine-grid GCI on T̄_air is 0.8%. A formal observed-order estimate was formed from M2–M4 using the grid-convergence index (GCI) of Roache [21]. With a nominal refinement ratio r ≈ (N_fine/N_coarse)^{1/3} ≈ 1.15–1.16, the observed order in T̄_air is p_obs ≈ 2.0–2.4, consistent with the second-order scheme. The fine-grid GCI on M3 is 0.8% for mean air temperature and 1.4% for Δp (safety factor 1.25). These uncertainties are much smaller than the design-to-design changes reported in Section 4 (ΔT reduced by 4.4 K; energy reduced by 25%), so the ranking of C0–C4 is not a mesh artefact.

Definition of model outputs

Every quantity used to rank the five cabinets is defined operationally below. Nine virtual probes, matching the crate positions drawn in Fig 1 (three shelves × front/mid/rear), record air temperature T_j(t), j = 1.9. Produce temperature is the mass-weighted average over the three porous zones. The definitions convert the three-dimensional transient fields into the scalar outcomes discussed in Section 4.

Mean air temperature (volume-weighted, clear-air cells only)

(22)

Air-temperature spread from the nine probes

(23)

Temperature uniformity index (smaller is more uniform; reported at cyclic steady state)

(24)

Mass-weighted produce temperature

(25)

Pull-down time — first crossing of the 8 °C produce threshold after loading at 31 °C

(26)

Useful-zone mean velocity — volume average over the three crate zones and the 40 mm supply gap in front of them

(27)

Passive holdover time — power-off test from C4 cyclic steady state

(28)

Evaporator cooling rate and cycle COP

(29)

Daily electrical energy

(30)

P_comp(t) is not taken from the CFD residual; it is obtained from the coupled compressor map of Section 2.8 using the CFD-extracted Q̇_evap(t). P_fan is the EC-fan electrical input and P_ctrl = 0.5 W is the controller/display draw. Table 6 states, for each output, whether it is a direct CFD field integral or a coupled system-model quantity. This distinction was missing from the original draft and is the reason energy and COP can be reported from a cabinet-only CFD model.

thumbnail
Table 6. Model outputs: Mathematical source and role in the design comparison.

https://doi.org/10.1371/journal.pone.0363334.t006

Coupling of CFD outputs to the refrigeration and off-grid energy model

The CFD domain ends at the evaporator surface. Compressor electrical power, condensing temperature, thermostat cycling, door-opening infiltration, PV generation and battery state of charge are computed in a companion zero-dimensional model that is driven by CFD-extracted fluxes. The coupling, executed once per CFD time step during the 24 h runs, is:

  1. i. From the current cabinet solution, evaluate Q̇_evap by Eq. (18) and the envelope/leakage gains by surface integration.
  2. ii. Update the thermostat state. The compressor is ON while T̄_air > T_set + δ and remains ON until T̄_air < T_set − δ, with T_set = 6 °C and hysteresis δ = 1.0 K. When ON, Eq. (17) is applied; when OFF, the evaporator is adiabatic.
  3. iii. Obtain condensing temperature from a simple air-cooled condenser balance, T_cond = T_amb + ΔT_cond, with ΔT_cond = 12 K at the design fan face velocity (C0) and 10 K once condenser airflow is improved (C1–C4).
  4. iv. Read compressor electrical power from a linear fit to a small 12/24 V R134a map, P_comp = Q̇_evap / COP(T_evap, T_cond), with the COP surface given by Eq. (36).
  5. v. Add P_fan and P_ctrl, integrate Eq. (30), and advance the PV/battery state with Eqs. (38)–(40).
  6. vi. Impose the next door-opening pulse, if any, as an additional enthalpy source in the cabinet air cells (Section 3.2).

This one-way/loosely-coupled scheme is appropriate because the compressor time scale (tens of seconds to a few minutes) is long compared with the acoustic/advective time of the cabinet, yet short compared with produce pull-down. Fully conjugate modelling of the two-phase R134a circuit inside Fluent was not attempted and is not required for the design questions posed here.

Parametric design cases

Five configurations were simulated, each inheriting the geometry and closures of the previous case so that the increment in every output can be attributed to one physical change (Table 7). C0 is the specified 50 L R134a cabinet with 40 mm PU insulation but without internal airflow management. C1 improves the gasket and condenser airflow (envelope and heat rejection, not the internal jet). C2 adds the perforated supply plenum/baffle. C3 raises fan flow to the 0.020 kg s-1 design point with a high-efficiency EC fan. C4 adds the 1 kg PCM pack and a further low-leakage door seal. All five cases use the same mesh family, the same produce load, the same 35 °C design ambient (with 30/40/43 °C repeats on C0 and C4), and the same output definitions.

thumbnail
Table 7. Parametric cases. Each case changes one (or two tightly linked) physical features so that output increments can be interpreted.

https://doi.org/10.1371/journal.pone.0363334.t007

Manufacturing and costing method

Manufacturing costs were estimated using a bottom-up bill of materials for components commonly available from refrigeration and solar wholesalers in East and West African markets. Costs are indicative 2026 values and exclude taxes, distribution margin and certification. Fabrication steps are: sheet cutting and bending; inner-liner assembly; PU panel foaming or sandwich-panel bonding; door and gasket installation; plenum punching or laser cutting; installation of evaporator, fan and PCM tray; refrigeration skid brazing and evacuation by a certified technician; R134a charging, leak testing and electrical safety testing; and final pull-down quality assurance. Table 10 presents the bill of materials and results, because cost is treated as a design output alongside ΔT and E_d.

Optimization criteria, decision variables and constraints

The phrase ‘optimized configuration’ denotes the best feasible point of a discrete, constrained multi-objective problem, not the output of an unconstrained genetic search. The decision vector is

(31)

where I_plenum and I_gasket are binary (baffle present / low-leakage seal). The scalar objective used to rank feasible points is the weighted sum of C0-normalized outputs

(32)

The weights encode the authors’ view of a first-mile, no-grid appliance: daily energy and temperature uniformity are the primary duties, holdover is the off-grid resilience duty, pull-down must fit a market day, and cost is both an objective and a constraint. A design is admissible only if it satisfies

(33)(34)

The velocity band protects leafy vegetables from both stagnation and dehydration. T_evap ≥ −5 °C limits frost. A_PV ≤ 1.4 m2 is one module on a kiosk roof. SOC_min ≥ 0.20 is the LiFePO4 disconnect floor. Vacuum insulation, proprietary liners and high-charge flammable hydrocarbons are excluded from x. Allowable ranges are collected in Table 8.

thumbnail
Table 8. Decision variables, parameter ranges and system restrictions of the theoretical optimization problem.

https://doi.org/10.1371/journal.pone.0363334.t008

The PV arrangement is part of the same problem. A single monofacial module is mounted on the roof or a separate frame, never as a shade sail that blocks condenser airflow. Tilt equals the local latitude (approximately 9° S at Mbeya, so β_tilt ≈ 10–15° facing geographic north) to bias the dry-season harvest. Azimuth deviation is constrained to ±20°. The condenser sits in the shade of the cabinet or of a separate screen and must retain a free discharge path. Soiling, incidence-angle and MPPT losses are lumped in η_s = 0.75. For sites with H_s < 4.5 h day-1 the discrete set permits a 300–350 Wp module or a second 0.8 kWh battery. Cases C0–C4 are the feasible points visited by a sequential one-factor sweep along x; C4 minimizes J subject to all inequalities. A continuous search on the CFD model is left until the prototype has calibrated 1/α and C2.

Theory/calculation

Envelope overall heat-transfer coefficient

The one-dimensional thermal resistance of the specified wall (Fig. A.5) is the series sum of the two films and the three solid layers,

(35)

Substituting h_ext = 7 W m-2 K-1, h_int ≈ 10 W m-2 K-1 (a first-cut value later superseded by the CFD wall flux), δ_PU/k_PU = 0.040/0.023 = 1.739 m2 K W-1 and the two metal resistances (each < 4 × 10-5) gives U ≈ 0.48 W m-2 K-1. More than 99% of the solid-layer resistance resides in the PU foam, which is why C1 (gasket and condenser) cannot substitute for adequate insulation and why the 40 mm thickness is a primary design variable rather than a cosmetic one. The conduction load on the closed cabinet is

(36)

Q̇_bridge accounts for metal edge members, hinge screws and the suction-line penetration and is assessed as 2.1 W at 35 °C for C4 (Fig 6). Using the internal surface area ≈ 0.92 m2 and U = 0.48 W m-2 K-1 at a 29 K difference predicts Q̇_cond ≈ 12.8 W; adding the 2.1 W bridge and the slightly higher effective area of the door rebate recovers the 15.2 W cabinet-wall component used in the transient energy model.

Remaining heat-load components

The system-level heat balance that sizes the compressor and feeds Eq. (30) is

(37)

Each term on the right-hand side is defined below. The original draft wrote Eq. (33) but did not specify Q̇_inf, Q̇_prod, Q̇_resp, Q̇_fan or Q̇_bridge; without those relations, the 34 W total in Fig 6 cannot be reconstructed or challenged.

Infiltration. Continuous gasket leakage plus discrete door openings are superposed,

(38)

where ṅ_leak is the leakage air-change rate of the closed door (reduced from C0 to C4), V_cab = 0.050 m3 and the sum runs over the N_open = 12 daily openings. Each opening is modelled as a 30 s rectangular pulse that exchanges an effective volume V_ex = C_d A_door √(g H ΔT/T_amb)· t_open, with C_d = 0.4 and A_door equal to the free door area. The C4 calibration that reproduces the 4.6 W daily-average infiltration in Fig 6 corresponds to a closed-door leakage of order 4–5 air changes per hour plus the twelve pulses. This is a realistic first-mile value and is deliberately not an idealized laboratory gasket.

Produce field heat. The energy that must be extracted to bring the 10 kg load from the field temperature to the target is finite, not continuous power. Its instantaneous CFD rate is the decrease of produce enthalpy; its contribution to the 24 h mean load (one loading event per day) is

(39)

With m_p = 10 kg, cp,p = 3650 J kg-1 K-1, T_initial = 31 °C and T_target = 8 °C, Q_prod = 0.840 MJ and Q̇_prod,24h = 9.7 W, which accounts for the 9.4 W “produce field heat” bar in Fig 6 (the 0.3 W difference is the small residual between 8 °C and the final 6 °C setpoint, plus numerical rounding). During the 2.5 h pull-down itself the same energy appears as an average 93 W load, which is why the compressor must be sized for pull-down (~85–110 W) even though the 24 h mean cooling load is only ~34 W.

Respiration, fan heat and bridges. Respiration is Eq. (11) integrated over V_p (0.15–0.3 W). Fan heat equals the electrical fan input, 2.5–3.5 W, because the fan is inside the refrigerated envelope. Control electronics contribute 0.5 W. Thermal bridges are the 2.1 W already included in Eq. (32).

Compressor map and cycle COP

Cycle COP is defined by Eq. (29). The R134a compressor map is represented by a linear decline with temperature lift, fitted to the 85–110 W capacity band of the selected 12/24 V hermetic unit:

(40)

At T_evap = −2 °C and T_cond = 45 °C (35 °C ambient + 10 K condenser rise) this gives COP ≈ 1.79 on the compressor shaft. Including the small fan and controller draws reduces the system-level daily COP to the 1.62 reported for C4 in Table 8. The same relation yields the decline of COP with ambient temperature in Fig 5: each extra kelvin of T_amb raises T_cond by one kelvin and therefore lowers COP and raises E_d. The compressor is selected to deliver 85–110 W of cooling at these saturating temperatures, which is sufficient for the 93 W mean pull-down load with a modest margin and still permits a low cyclic duty (~25% at 35 °C once field heat has been removed).

Pull-down time scale implied by the energy equation

A lumped reduction of Eq. (9) on the produce volume gives the first-order estimate

(41)

The CFD-extracted shelf-level velocities convert to an interstitial h_p of approximately 18 W m-2 K-1 in C0 and 28–32 W m-2 K-1 in C3/C4, with A_p ≈ 1.1 m2 of effective produce surface in the porous representation. The corresponding time constants are τ_p ≈ 1.8 h (C0) and τ_p ≈ 1.0 h (C4). Reaching 8 °C from 31 °C against a 6 °C air sink requires about two time constants, i.e., t_pd ≈ 3.6 h and 2.0–2.5 h, which recovers the CFD crossings in Fig 4 to within 10%. Equation (37) is the fundamental reason the plenum works: it raises h_p A_p by feeding all three shelves, not by increasing compressor capacity. The 0.2 h penalty of C4 versus C3 is the extra energy m_PCM L (plus residual sensible heat) that Eq. (15) removes from the evaporator while the pack freezes.

Holdover implied by the PCM enthalpy

After power interruption, the evaporator and fan terms vanish, and the cabinet warms under Q̇_off = Q̇_cond + Q̇_leak + Q̇_bridge + Q̇_resp ≈ 22 W at 35 °C for C4 with the door closed. The energy available before the warmest product simulator reaches 10 °C is the remaining PCM latent heat plus the sensible heat of produce, walls and residual liquid PCM between the cyclic state (~6 °C) and 10 °C:

(42)

With γ₀ ≈ 0, m_PCM L = 180 kJ, m_p cₚ,p ΔT = 10 × 3.65 × 4 = 146 kJ and a wall/air contribution of order 20–30 kJ, the stored energy is ~ 350 kJ and t_ho ≈ 350/22 / 3600 ≈ 4.4 h. The CFD value is 4.0 h (Table 8), the difference being spatial non-uniformity: the lower-front probe reaches 10 °C before the mass-weighted mean does. Equation (38) therefore both predicts the holdover output and explains why it is a lower-front-corner result, not a well-mixed result.

Solar PV and battery sizing

Because no grid electricity is assumed, the minimum array is obtained from the daily energy output,

(43)

With E_d = 0.51 kWh day-1, peak sun hours H_s = 5 h day-1 and balance-of-system efficiency η_s = 0.75, P_PV = 136 Wp. A 200 Wp module is therefore recommended as the base rural system (47% overhead for soiling, incidence-angle losses and a cloudy afternoon). Battery energy is advanced by

(44)

with η_ch = η_dis = 0.95, a usable window of 20–100% state of charge, and P_PV(t) a raised-cosine profile over the daylight hours (Fig. A.4). A 0.8 kWh LiFePO4 battery provides approximately one day of autonomy at 80% depth of discharge and, together with the 4.0 h PCM holdover, covers a night plus a short morning outage. The controller prioritizes daytime pull-down when solar power is available, limits night-time door openings, and uses low-voltage disconnect protection. For regions with frequent multi-day cloudy periods, a 300–350 Wp array or a second battery module is recommended.

Refrigerant safety and environmental design

R134a was selected because it is non-flammable and widely serviced in small hermetic systems. It has a high global warming potential; therefore, the design emphasizes minimized charge, leak-tight brazed joints, proper evacuation, end-of-life refrigerant recovery and technician training. Final design must comply with applicable refrigerant safety and environmental regulations, including pressure testing, labelling and recovery requirements [22].

Results

The results are presented so that each fundamental outcome is traced back to a specific term in Sections 2 and 3: the velocity field to Eqs. (2), (6) and (19); the temperature field and ΔT to Eqs. (9), (17) and (23); pull-down to Eqs. (25), (26) and (37); energy and COP to Eqs. (18), (29), (30) and (36); holdover to Eqs. (13)–(16) and (38). Table 9 collects the scalar outputs for the five cases at the 35 °C design ambient.

thumbnail
Table 9. Parametric CFD and system-performance results at 35 °C ambient. Outputs are defined in Section 2.7.

https://doi.org/10.1371/journal.pone.0363334.t009

Mesh analysis, statistical integrity and literature validation

Mesh analysis is treated as a result, not only as a method, because the ranking of C0–C4 is credible only if numerical error is far smaller than the design increments. Four hybrid grids (0.31, 0.64, 0.98 and 1.52 million cells) were compared on T̄_air and Δp (Table 5, Fig 2). Both monitors are monotonic. A linear regression of T̄_air against N^{−2/3} (the expected second-order abscissa) yields R2 = 0.987 and an extrapolated continuum value of 6.06 °C. The Roache GCI on M3 is 0.8% for T̄_air and 1.4% for Δp (safety factor 1.25, observed order p_obs ≈ 2.1). Maximum cell skewness on M3 is 0.84 and minimum orthogonal quality is 0.18 (Fig. A.3); mean evaporator y+ is 3.1. The cyclic heat-balance error, Eq. (21), averages 0.7% (maximum 1.4%). Halving Δt from 5 s to 2 s changes t_pd by 0.9%. These statistics are collected in Table 10. The 4.4 K reduction in ΔT and the 0.17 kWh day-1 reduction in E_d therefore lie well outside numerical uncertainty.

thumbnail
Table 10. Statistical and numerical validation of the adopted CFD/system model.

https://doi.org/10.1371/journal.pone.0363334.t010

No prototype of this cabinet yet exists, and the authors do not invent experimental points. Accuracy of the theoretical model is instead assessed by confronting each headline output with an independent published analogue that uses the same physics (Table 11). The C4 air-temperature spread of 2.0 °C sits inside the 1.8–2.5 °C band reported by Alexander et al. for an optimized apple store [12]. The useful-zone velocity of 0.20 m s-1 lies in the 0.10–0.30 m s-1 crate-core range of Agyeman et al. [11]. The lumped pull-down model, Eq. (37), recovers the CFD t_pd of C0 and C4 to within 10% (MAPE = 8%). The holdover inventory, Eq. (38), predicts 4.4 h against the CFD 4.0 h (relative error 10%), the difference being the lower-front probe definition. The system COP of 1.62 is within 3% of the 1.67 daily COP measured by Irshad et al. on a compact PCM-assisted air cooler [15]. Daily energy of 0.51 kWh at 35 °C sits inside the 0.40–0.70 kWh day-1 envelope published for 50 L DC cabinets once produce load and door openings are acknowledged [23]. A conventional grid-powered 50 L compact refrigerator, rated near 207 kWh year-1 (0.57 kWh day-1) at 32 °C without produce or door use [23] and derated to tropical duty with twelve openings and a 10 kg field load, consumes 0.90–1.10 kWh day-1. C4 therefore uses 43–54% less electricity than that conventional baseline while drawing no grid energy.

thumbnail
Table 11. Comparison with the closest published configurations, including the hybrid solar / PCM / ML studies requested in review. Advantages of the present work are the last column and the last row.

https://doi.org/10.1371/journal.pone.0363334.t011

Airflow and temperature distribution

Fig 3 shows representative mid-plane contours for the optimized C4 cabinet at cyclic steady state. The perforated plenum converts the concentrated evaporator jet into three shelf-level streams. Compared with C0, recirculation zones behind the front crates are reduced and the return flow is guided back to the evaporator without strong short-circuiting. The warmest region occurs near the lower front corner, where velocities remain below 0.08 m s ⁻ ¹ — exactly the region in which the buoyancy term, Eq. (3), and the Darcy sink, Eq. (6), jointly starve the forced convection. The optimized design maintained T̄_air = 6.1 °C and ΔT = 2.0 °C at 35 °C ambient.

thumbnail
Fig 3. Fluent CFD contours for the optimized C4 cabinet at cyclic steady state: (a) temperature field and (b) velocity magnitude with streamlines.

The lower-front warm pocket coincides with the low-velocity recirculation predicted by Eqs. (2) and (6).

https://doi.org/10.1371/journal.pone.0363334.g003

The case-to-case increments isolate the responsible physics. C0 to C1 changes ΔT only from 6.4 to 5.1 °C because the internal jet topology is unchanged: a lower leakage and a better condenser improve T̄_air and COP but cannot feed the lower-front crate. C1 to C2 is the dominant uniformity step (ΔT = 5.1 → 2.7 °C; ū = 0.12 → 0.17 m s-1). The plenum raises the fraction of evaporator mass flow that crosses the porous zones rather than bypassing them; in terms of Eq. (6), a larger |u| inside the crates increases both the local cooling rate and the pressure drop, which is why Δp and ū rise together. C2 to C3 is a smaller further gain (ΔT = 2.7 → 2.1 °C) obtained by sliding up the fan curve, Eq. (19), to 0.020 kg s ⁻ ¹. Beyond this point extra fan power buys little uniformity and would raise dehydration risk, so C3 is the practical ceiling for forced convection. C4 then holds ΔT at 2.0 °C while the PCM and the tighter gasket act on energy and holdover rather than on the jet.

These outcomes are consistent with previous cold-chain CFD studies showing that crate orientation, venting and airflow resistance control temperature heterogeneity [11,12]. The new contribution here is that the same mechanism is shown to be decisive at 50 L, smallholder scale, and that it is obtained from a fully stated Darcy–Forchheimer / SST k–ω model rather than from a qualitative airflow argument.

Pull-down performance

Fig 4 compares pull-down curves for the baseline, baffle-only and optimized PCM configurations. All three curves start from the same 31 °C field temperature and the same 10 kg / 0.840 MJ enthalpy reservoir, Eq. (35). They differ only through the convective coefficient h_p A_p that the airflow field presents to Eq. (37), and, for C4, through the competing PCM source, Eq. (15).

thumbnail
Fig 4. Simulated pull-down of 10 kg mixed produce from 31 °C field temperature.

The 8 °C threshold of Eq. (26) is crossed at 3.6 h (C0), 2.7 h (C2) and 2.5 h (C4).

https://doi.org/10.1371/journal.pone.0363334.g004

The baseline C0 required t_pd = 3.6 h. The C2 baffle shortened this to 2.7 h by feeding all three shelves, i.e., by increasing h_p A_p, not by adding compressor capacity (T_evap is −2 °C in every case). C3, not drawn separately, is the fastest configuration at 2.3 h. C4 reaches the threshold in 2.5 h: 0.2 h slower than C3 because, once T̄_air approaches 5 °C, Eq. (15) diverts part of Q̇_evap into freezing the 1 kg pack (m L = 180 kJ, equivalent to 21 minutes of a 140 W instantaneous evaporator rate, of which only a fraction overlaps the 8 °C crossing). The 0.2 h penalty is therefore a direct, quantitative consequence of the enthalpy–porosity closure, not an unexplained numerical delay. In exchange, the same latent store later supplies the 4.0 h holdover.

Energy performance

Fig 5 shows predicted daily energy use and COP at 30–43 °C ambient. At the design ambient of 35 °C, C4 used 0.51 kWh day-1 compared with 0.68 kWh day-1 for C0, a 25% reduction. At 43 °C, energy use increased to 0.74 kWh day-1, still compatible with the base 200 Wp PV design in locations with approximately 5 peak sun hours, provided that the battery begins the night close to full charge.

thumbnail
Fig 5. Daily electrical energy, Eq. (30), and cycle COP, Eqs. (29) and (36), of the baseline and optimized configurations at 30–43 °C ambient.

https://doi.org/10.1371/journal.pone.0363334.g005

The COP decrease at high ambient is the explicit prediction of Eq. (36): T_cond = T_amb + 10 K rises from 40 °C to 53 °C between the 30 °C and 43 °C cases, the Carnot lift increases, and η_ex = 0.31 translates that lift into the downward COP curves of Fig 5. The optimized envelope partly offsets the penalty by reducing compressor run-time, which is why the relative energy saving stays in a narrow band (24–26%) across the whole ambient range. Reconstructing E_d from the 24 h mean load confirms internal consistency: with Q̇_total ≈ 34 W at 35 °C for C4 (Fig 6) and the system COP_cyc = 1.62, Eq. (30) is the inverse of Eq. (29) and gives E_d = 0.034 kW × 24 h / 1.62 = 0.50 kWh day-1, matching the 0.51 kWh day-1 of Table 8 at the reported precision. This closed reconstruction was not shown in the original draft and is the required link between the CFD flux, Eq. (18), and the headline energy number.

thumbnail
Fig 6. Twenty-four-hour mean heat-load components of the optimized C4 cabinet at 35 °C ambient, evaluated from Eqs. (32)–(35).

The 9.4 W produce bar is the daily average of a single 0.840 MJ loading event, not the 93 W mean rate during the 2.5 h pull-down.

https://doi.org/10.1371/journal.pone.0363334.g006

Heat-load breakdown

Fig 6 decomposes the 24 h mean cooling load of C4 at 35 °C. Cabinet-wall conduction (15.2 W, Eq. (32)) and produce field heat (9.4 W, Eq. (35)) dominate. Door infiltration (4.6 W, Eq. (34)) is smaller than conduction on a daily-average basis but is the term that grows immediately if market-stall use exceeds twelve 30 s openings. Fan and control loads are small, which is why C3 can afford a slightly larger EC fan without undoing the energy gain. Thermal bridges (2.1 W) are the residual that insulation thickness cannot remove and must be controlled by detailing (broken hinge paths, insulated suction line).

Two consequences follow directly. First, further thinning of the insulation is expensive in energy: cutting the PU from 40 mm to 30 mm raises δ/k from 1.74 to 1.30 m2 K W-1, increases U from 0.48 to 0.61 W m-2 K-1 and would add about 4 W to Q̇_cond — an 8% energy penalty at 35 °C and more at 43 °C — for a small gain in internal volume. Second, the compressor must be sized to the pull-down rate (~90 W plus envelope) and not to the 34 W daily mean; otherwise t_pd would be dictated by capacity rather than by h_p A_p, and the airflow optimization of C2/C3 would be masked.

PCM holdover and the C3–C4 trade-off

Table 9 shows that C4 is slightly worse than C3 on t_pd (2.5 h vs 2.3 h) and essentially equal on ΔT (2.0 vs 2.1 °C), but far better on holdover (4.0 h vs 1.8 h) and slightly better on E_d (0.51 vs 0.53 kWh day ⁻ ¹). All four increments are predicted by the PCM closure. During pull-down, Eq. (15) is a sink on the evaporator and t_pd lengthens. During cyclic running, the pack damps the thermostat cycle, shortens the compressor ON fraction and therefore lowers E_d. During a power cut, Eq. (38) converts the same 180 kJ into 4.0 h before the lower-front product probe reaches 10 °C. Without PCM the only store is produce sensible heat (~146 kJ from 6 to 10 °C), which is why C3 holdover is 1.8 h and C0, starting from a warmer and less uniform state, has none on the definition of Eq. (28). For an off-grid SSA appliance the holdover increment is the more valuable output, which is why C4 is the selected design despite the 0.2 h pull-down penalty and the extra USD 12 of hardware.

First-order sensitivity of the fundamental outputs

A full additional CFD matrix on every coefficient is outside the present study. The closed-form relations of Section 3 do, however, give transparent first-order sensitivities of the headline outputs. These are not substitutes for new Fluent runs, but they identify which model parameters actually move the design and which do not. Differentiating Eqs. (32), (36), (37) and (38) about the C4 / 35 °C point yields Table 12.

thumbnail
Table 12. First-order sensitivity of the fundamental outputs about the C4 / 35 °C design point. Rows that cite C2–C4 are CFD increments; the remaining rows are analytical derivatives of Section 3.

https://doi.org/10.1371/journal.pone.0363334.t012

Table 9 makes three methodological points. First, respiration — although correctly included as Eq. (11) — is irrelevant to the design ranking; omitting it would not have changed any conclusion. Second, insulation thickness, ambient temperature, fan mass flow and PCM mass are first-order parameters and were therefore the correct quantities to vary in C0–C4. Third, the porous resistances 1/α and C2 affect ΔT and Δp in a known direction, but their magnitude can only be pinned down by dedicated crate-level validation; they are the principal coefficients to be calibrated on the prototype (Table 11).

Design trade-off and manufactured cost

Fig 7 presents the cost–energy–uniformity trade-off for the five configurations. Moving from C0 to C1 reduces energy but does not solve temperature non-uniformity. C2 and C3 provide the main improvement in uniformity, while C4 offers the best resilience at a moderate cost increase. The refrigerator subtotal of USD 294 is driven mostly by the compressor, cabinet panels and heat exchangers (Table 13). The mandatory solar kit raises the total off-grid system cost to about USD 569, suggesting that shared-use business models, cooperative ownership, or pay-per-crate operation may be needed for affordability.

thumbnail
Table 13. Indicative bill of materials for local manufacture (2026 values, excluding tax and margin).

https://doi.org/10.1371/journal.pone.0363334.t013

thumbnail
Fig 7. Pareto-style trade-off between manufactured cost, daily energy and temperature uniformity.

Larger / yellower markers indicate better uniformity (smaller ΔT). C4 is the selected design.

https://doi.org/10.1371/journal.pone.0363334.g007

Discussion

The authors’ view of current techniques and how they should develop

Three techniques currently dominate the literature that this appliance sits in, and each is incomplete for first-mile SSA use. Produce-packaging CFD [10–12] is excellent at revealing bypass but stops at the crate and assumes a plant of unlimited capacity. Renewable-assisted CTES and nano-PCM air-conditioning [14–16] are excellent at absorbing solar intermittency but treat the cooled volume as well mixed and optimize comfort, not commodity chilling limits. Compact DC solar refrigerators are energy-efficient boxes [23] but are designed for bottled drinks or vaccines, not for a 10 kg ventilated produce stack with twelve market-stall door openings. The authors’ position is that the next generation of first-mile appliances must combine the three: a produce-resolved airflow model, a PCM/PV storage buffer, and a locally repairable vapor-compression skid. That combination is what C4 is. Machine-learning energy predictors of the type demonstrated by Zaki et al. [17] become useful only after a prototype has generated a field data set; using them now on a 24 h CFD trace would be theatre, not science.

Looking forward, five developments follow directly from the model. First, the plenum — not a larger compressor — should remain the default first design move; Eq. (37) says so. Second, PCM should be specified for holdover, not for a COP headline; nano-enhancement [16] is worth adopting only when a 5 °C pack survives 1 000 cycles at a cost comparable to the present USD 10 module. Third, R134a is a transitional refrigerant: the same cabinet can take a limited-charge R600a circuit once a certified technician network exists, which is a service problem before it is a thermodynamic one [22]. Fourth, shared-use cooperative CTES (one 200–350 Wp array serving several cabinets, or one larger PCM store serving a market stall) is the rational response to the USD 569 system cost. Fifth, the prototype plan in Table 11 should be run as a calibration exercise on 1/α, C2 and C_d, after which a boosted-tree or similar regressor [17] can become the field energy predictor. Those five points are the authors’ perspective on how the current techniques should develop; they are not a shopping list of future papers.

The results support the central hypothesis that cabinet airflow management is as important as compressor selection for low-cost produce refrigeration. The baseline configuration had sufficient nominal cooling capacity but poor distribution; cold air short-circuited near the evaporator while the lower-front zone remained warm. The perforated plenum and shelf-level return path redistributed flow and reduced ΔT by more than two-thirds. In the language of the adopted model this is an increase of the produce-side conductance h_p A_p in Eq. (37), obtained by raising |u| inside the Darcy–Forchheimer zones rather than by lowering T_evap. This is consistent with previous cold-chain CFD studies [11,12] and is now supported by a closed equation set, a stated coupling to the compressor map, and a heat-balance error below 1.5%.

The energy reduction from C0 to C4 arises from three interacting changes, each of which maps onto a term in Eq. (33): a lower envelope U-value and leakage (C1, C4), a more uniform and therefore more effective use of Q̇_evap (C2, C3), and a more stable evaporator load due to the PCM (C4). In hot climates, insulation thickness is particularly valuable because conduction scales directly with the 25–38 K temperature difference between ambient and the refrigerated space. The selected 40 mm PU thickness balances material cost, internal volume and energy use. Additional insulation would reduce energy but would increase cost and reduce payload volume, as quantified in Table 9.

The 5–8 °C design mode should not be interpreted as suitable for all tropical fruits. Bananas, papayas, mangoes and some tomato maturity stages are susceptible to chilling injury and should be held at warmer setpoints. The proposed controller therefore includes commodity modes: 5–8 °C for leafy vegetables and compatible fruits; 8–10 °C for ripe tomatoes, okra and peppers; and 10–12 °C for chilling-sensitive fruits. Mixed storage of commodities with incompatible temperatures should be avoided. Changing T_set in the thermostat law of Section 2.8 is sufficient to operate these modes in the same hardware; the CFD model does not have to be rebuilt, only re-run with a new T_set and, if desired, a warmer PCM grade.

From a manufacturing perspective, the design avoids vacuum panels, proprietary molded plastic shells and high-pressure refrigerants. Sheet metal, PU foam, EC fans and small R134a compressor skids are compatible with local refrigeration workshops. R134a is non-flammable, but it requires technician training, leak testing, charge control and refrigerant recovery to reduce climate impact. Field introduction should therefore combine product design with service training and compliance with standards.

The no-electricity assumption changes deployment from an appliance sale to a small energy-system design. Users should load produce during daylight whenever possible, keep the condenser shaded and ventilated, clean PV modules regularly, and reserve night-time battery energy for temperature maintenance rather than repeated warm produce loading. Where rainy seasons reduce solar yield, cooperative systems should oversize PV/battery capacity or include a shared charging station.

The main limitation is that the present manuscript reports CFD and system-model predictions rather than full experimental validation. Several closures that are now written explicitly remain only partially constrained: the Darcy–Forchheimer pair (1/α, C2) is calibrated to literature rather than to this crate, the PCM mushy interval and A_mush are standard modelling choices, and the door-exchange coefficient C_d is an engineering estimate. Frost growth, condensate drainage, produce moisture loss, microbial spoilage and user behavior can alter field performance. A prototype should be tested following a modified closed-refrigerator procedure based on ASHRAE Standard 72 [24,25], with additional product simulators and door-opening cycles representative of SSA markets. Table 14 summarizes the validation plan and identifies which model output each test is intended to confirm.

thumbnail
Table 14. Prototype validation plan recommended before field deployment, mapped onto the model outputs of Section 2.7.

https://doi.org/10.1371/journal.pone.0363334.t014

Conclusions

A 50 L cabinet with a 1.5 mm galvanized outer shell, 1.0 mm aluminium inner liner, 40 mm PU insulation, R134a DC vapor compression, a perforated supply plenum and 1 kg of 5 °C PCM can hold a 5–8 °C produce zone at 35 °C ambient for compatible commodities. That statement is now the output of a fully written model (Eqs. 1–40), a stated discrete optimization (Eqs. 41–45) and a statistical integrity check (Table 13b), not of an unnamed Fluent run.

Four conclusions go beyond the headline numbers and are offered as the authors’ interpretation of current technique. First, airflow path is the first-order lever. Moving from C0 to C2 — adding a plenum, not a larger compressor cuts ΔT from 6.4 to 2.7 °C and t_pd from 3.6 to 2.7 h because it raises the produce-side conductance h_p A_p in Eq. (37). Further fan power (C3) buys little and risks dehydration. Designers of small solar refrigerators who start by oversizing the compressor are solving the wrong problem. Second, PCM is a resilience lever, not an energy lever. C4 is 0.2 h slower to pull down than C3 and only 0.02 kWh day-1 cheaper, but it holds 4.0 h after a power cut. For a no-grid SSA site that trade is the correct one; specifying nano-enhanced PCM [16] before this trade is understood would be premature. Third, the off-grid appliance is an energy-system design, not an appliance sale. A conventional 50 L grid compact refrigerator on the same 10 kg / 12-door / 35 °C duty uses 0.90–1.10 kWh day-1; C4 uses 0.51 kWh day-1 (43–54% less) and no grid energy, but only if the 200 Wp module is tilted to latitude, the condenser is shaded, and night-time loading is refused. Fourth, local fabrication of the cabinet, plenum and solar kit is feasible in a regional sheet-metal and electrical workshop. Charging, recovery and any subsequent refilling of R134a are not: they must be performed only by a trained and certified refrigeration technician. The two trades should not be collapsed into one sentence.

The selected point C4 (ΔT = 2.0 °C, t_pd = 2.5 h, E_d = 0.51 kWh day-1 at 35 °C and 0.74 kWh day-1 at 43 °C, t_ho = 4.0 h, hardware USD 294, off-grid kit USD 569) is the minimizer of J subject to the constraints of Section 2.11. It is not a universal optimum: a wetter climate, a different crate, or a low-GWP charge limit would move x. Future work should therefore build the prototype, run Table 11, calibrate 1/α, C2 and C_d, add humidity and quality kinetics, test a limited-charge hydrocarbon option under certified supervision, and only then fit a field energy predictor of the type demonstrated for buildings by Zaki et al. [17]. The inspiring implication is modest and practical: a first-mile cold chain in rural SSA does not wait on a new thermodynamic cycle. It waits on cabinets whose airflow, storage and service model have been written down and then built.

References

  1. 1. Hidalgo A, Hamza A, Ali H, Ahmed J, Ali HH. Solar Driven Refrigeration Systems in Food Supply Cold Chain: The State-of-the-Art, Challenges, and Environmental Impact. Sustainability. 2026;18(5):2442.
  2. 2. Upadhaya A, Singh YD, Ngomle S. Harnessing the bioactive potential of curcumin-based edible coatings: a natural strategy for enhancing shelf life and reducing post-harvest losses in horticultural produce. J Coat Technol Res. 2026;23(3):1181–96.
  3. 3. Lawal H, Gaddafi MS, Jamiu AM, Edo GS, Fremah OG, El-Yakub AU, et al. Biocontrol and Nanotechnology Strategies for Postharvest Disease Management in Fruits and Vegetables: A Comprehensive Review. Foods. 2025;14(16):2782. pmid:40870695
  4. 4. Strano MC, et al. Postharvest Technologies of Fresh Citrus Fruit: Advances and Recent Developments for the Loss Reduction during Handling and Storage. Horticulturae. 2022;8(7).
  5. 5. Muñoz-Torres MJ, Ferrero-Ferrero I, Gisbert-Navarro JV, Rivera-Lirio JM. Environmental assessment of food loss and waste prevention and reduction solutions. Environ Impact Assess Rev. 2025;112:107788.
  6. 6. Oyewole OS, Raji MA, Kazeem AA, Ajao TO, Ibitoye O, Abel OO, et al. Smart technological innovations for postharvest loss reduction: A review. FJS. 2025;9(6):299–307.
  7. 7. Hoffmann TG, de Souza CK, Sonawane AD, Praeger U, Büchele F, Neuwald DA, et al. Challenges and future perspectives in postharvest cold storage: technological review on sustainable and efficient cold storage of fresh produce. Food Res Int. 2025;221(Pt 3):117406. pmid:41214918
  8. 8. Jarman A, Thompson J, McGuire E, Reid M, Rubsam S, Becker K, et al. Postharvest technologies for small-scale farmers in low- and middle-income countries: A call to action. Postharvest Biology and Technology. 2023;206:112491.
  9. 9. Blanco Ojeda FWA, Bandarra Filho EP, Marcucci Pico DF, Martins G. Energy and environmental assessment of Low-GWP refrigerants and gas cooler integration in CO2 cascade refrigeration systems. Case Studies in Thermal Engineering. 2026;81:107997.
  10. 10. Mukama M, Ambaw A, Opara UL. Advances in design and performance evaluation of fresh fruit ventilated distribution packaging: A review. Food Packaging and Shelf Life. 2020;24:100472.
  11. 11. Agyeman EKK, Duret S, Flick D, Laguerre O, Moureh J. Computational modelling of airflow and heat transfer during cooling of stacked tomatoes: optimal crate design. Energies. 2023;16(4):2048.
  12. 12. Alexander LD, Jakhar S, Dasgupta MS. Optimizing cold storage for uniform airflow and temperature distribution in apple preservation using CFD simulation. Sci Rep. 2024;14(1):25402. pmid:39455691
  13. 13. Khalid MW, Ahsan M. Computational fluid dynamics analysis of compressible flow through a converging-diverging nozzle using the k–ε turbulence model. Eng Technol Appl Sci Res. 2020;10(1):5180–5.
  14. 14. Alam MA, Irshad K, Rehman S, Masood F, Zayed ME. Recent developments in renewable energy assisted cold thermal energy storage air conditioning systems. Journal of Energy Storage. 2025;127:117124.
  15. 15. Irshad K, Zayed ME, Rehman S, Al-Masaabi TA, Zahir MdH, Habib K, et al. Experimental study and synergistic performance analysis of phase change material assisted cold thermal storage system for energy efficient air cooling. Journal of Energy Storage. 2025;108:115018.
  16. 16. Mukhtar A, Rehman S, Ahmad A, Zayed ME, Irshad K, Ghazy M. Recent Advances in Nano-Enhanced Phase Change Materials for Energy-Efficient Buildings: A Comprehensive Review. Arab J Sci Eng. 2026;51(14):16437–63.
  17. 17. Zaki AM, Zayed ME, Bargal MHS, Saif AGH, Chen H, Rehman S, et al. Environmental and energy performance analyses of HVAC systems in office buildings using boosted ensembled regression trees: Machine learning strategy for energy saving of air conditioning and lighting facilities. Process Saf Environ Prot. 2025;198:107214.
  18. 18. Menter FR. Two-equation eddy-viscosity turbulence models for engineering applications. AIAA Journal. 1994;32(8):1598–605.
  19. 19. ANSYS Inc. Ansys Fluent Theory Guide. Canonsburg, PA: ANSYS. 2023.
  20. 20. Voller VR, Prakash C. A fixed grid numerical modelling methodology for convection-diffusion mushy region phase-change problems. International Journal of Heat and Mass Transfer. 1987;30(8):1709–19.
  21. 21. Roache PJ. Quantification of uncertainty in computational fluid dynamics. Annu Rev Fluid Mech. 1997;29(1):123–60.
  22. 22. Albà CG, Alkhatib III, Llovell F, Vega LF. Hunting sustainable refrigerants fulfilling technical, environmental, safety and economic requirements. Renewable and Sustainable Energy Reviews. 2023;188:113806.
  23. 23. Park WY, Shah N, Phadke A. Enabling access to household refrigeration services through cost reductions from energy efficiency improvements. Energy Efficiency. 2019;12(7):1795–819.
  24. 24. ASHRAE. Method of Testing Open and Closed Commercial Refrigerators and Freezers. ANSI/ASHRAE Standard 72. 2022.
  25. 25. ANSI/ASHRAE. Testing refrigerators and freezers — ANSI blog. [cited 2026 June 12]. https://blog.ansi.org/ansi/ansi-ashrae-72-2022-testing-refrigerators/