Abstract
The impact of the topological formation of wind farms upon the lightning induced overvoltages injected into the grid was not covered earlier in literature. However, this topic is highly important to be investigated to allow the usage of the most reliable topology against lightning strikes. For such reason, the paper investigates this point with consideration of most damaging cases as lightning strikes to multi-blades. The testing used ATP software for four main topologies, radial, single-sided ring SSR, double sided ring and star topology. The features defining the similarities in response and the variance range between these topologies were recorded and analyzed. The multi-blade strikes gave an expected increase of 15% to 100% in the injected overvoltage to the grid for all topologies. The star topology showed the most reliable performance by allowing the least injected overvoltage to the grid. The percentage of reduction in the magnitude of the injected overvoltages reached 50.78%, 66.07% and 89.04% for SSR, DSR and star topology respectively with respect to radial topology. Recommendation was provided for design engineers to consider star topology during design phase in terms of more reliable lightning protection.
Citation: Wadie F, Almuflih AS, Elbarybary ZMS, Eliyan T (2024) Variance in multi-blade induced lightning overvoltages among different wind farm topologies. PLoS ONE 19(9): e0308449. https://doi.org/10.1371/journal.pone.0308449
Editor: Amit Kumar, University of Cagliari, ITALY
Received: March 13, 2024; Accepted: July 24, 2024; Published: September 5, 2024
Copyright: © 2024 Wadie et al. This is an open access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.
Data Availability: All relevant data are within the manuscript.
Funding: This work is supported by the Deanship of Scientific Research, King Khalid University. through General Research Project under Grant number (RGP.2/33/45) The funders had no role in study design, data collection and analysis, decision to publish, or preparation of the manuscript.
Competing interests: The authors have declared that no competing interests exist.
Introduction
The transformation to green energy power generation has always faced the challenge of the random nature for natural sources for renewable energy [1–9]. Such natural sources have mandated specific locations for renewable energy resources to be feasible for implementation, which in turn endangered these sources by being exposed to hazardous weather conditions. Specifically, wind farms have been under the impact of lightning strikes requiring protective measures to be taken for their protection [10–13]. The most exposed element within wind farms, is the blades of their turbines. That is due to being exposed with a very long height in exposed areas [14–18]. A direct lightning strike on the tip of one the blades of the wind turbine will lead to the incidence of a surge that propagates across the tower structure causing a gigantic rise in potential across tower elements [16–23]. The impact of these strikes upon the different elements of the wind farm have been under study with researchers focusing upon the impact across tower structure [15–18] or across the grounding system [15,24,25] and across the remaining electrical network of the wind farm [26–30]. However, researches in [26–30] focused upon the lightning induced within wind farms of radial topology only and other topologies were not considered. For this reason, the paper intends to focus on impact of the lightning induced surges in different wind farm topologies. Four topologies are considered in this research; radial, single-sided ring (SSR), double-sided ring (DSR), and star topologies [31,32]. This would allow the viewing of the degree of variance of the impact of lightning strikes from one topology to another. Hence, it could be defined which the wind farm topologies that provide more reliable response in terms of the lightning induced surges.
A second aspect that should be considered is the type of the lightning strikes including positive, and negative lightning strikes [33–36]. However, not only the type of the strike affects the resulting induced overvoltages, but also the possibility of hitting multi-blades of the turbine. [10,16,17]. The strike which hit multi-blades could be initiated by scenarios including the sweeping of lightning flash from one blade to another as a result of the blade’s rotation, branching of the lightning strike to reach more than one blade or subsequent lightning strikes to other blades. Even though the occurrence of a strike that hits multi-blades has a low probability but it still relatively dangerous once it happens. That’s due to the significant damages to the blades and economic loss are greater than those under the lightning strike to single-blade [10,16]. Hence, this study will consider the dual impact of changing the type of wind topology and the possibility of striking a multi-blade upon the resulting overvoltages. ATP/EMTP simulation platform was used in this study. The main contributions of the paper include:
- Investigating a rare topic in literature which is the impact of changing the topology of the wind farm upon the magnitude of the resulting lightning induced overvoltages
- Extending the investigation to include the variance in results for lightning strikes and possible strikes to multi-blades which represent highly damageable scenarios.
- Defining the levels of variation in the magnitude of resulting overvoltages for different wind farm topologies under different multi-blade scenarios.
- Evaluating the response within each topology under extreme multi-blade conditions allowing to present conclusions that would assist design engineers in selecting the most suitable wind farm topology during the design phase.
The rest of this paper is arranged in the following order. The data and structure of the system selected to be under investigation, it’s modeling process upon ATP/EMTP are sequentially presented in sections of system under study and modeling of the system. The results of the simulation in different topological cases and under different striking conditions are presented in simulation results section and later analyzed in analysis and discussion section. Finally, conclusions are drawn in conclusions section.
System under study
The system used for testing was based on the data from a real 550 MW wind farm system located in Zaafrana, Egypt. The system consists of 700 wind turbines which were assumed to be identical with each of them connected to a 1 MVA 690 V/22 kV-transformer. 200 m cables were used to connect each two turbines following each other in sequential order. A 220/22 kV substation ties the farm to the grid. The data of the elements of the introduced system will remain unchanged but the topology of the system will be changed to examine the variance in their response during lightning strikes as previously defined to be one of the aims of the paper. The testing topologies include radial, SSR, DSR and star topologies as shown in Fig 1. The lengths of the feeders are as follows; F1 = 8 km for all topologies. F2 = 10.4 km in SSR topology and 6.5 km in DSR topology, F3 = 1 km. The lengths of the cables will be 200 m for all topologies except for star topologies due to its design nature that require the cables connected to each turbine to be of different lengths. The lengths of cables for star topology follows the next pattern; 200 m for W2 and W8, 400 m for W3 and W9, 600 m for W4 and W10, and so on till W7 and W13. The modifications done is based upon those presented in [37]. The modeling of the elements of the system is discussed in the next section. The circuit diagram used for modeling star topology on ATP software is shown in Fig 2.
Topologies of wind farm (a) Radial (b) Single sided ring (b) Double sided ring (d) Star.
Modeling of the system
Modeling of the wind turbine
Tower and blades of the wind turbine.
The physical formation of blades of tower body of the wind turbine was used build its model. Therefore, the surge impedances of the tower and blade were driven from cylindrical and conical equations of the electromagnetic field theory as given in (1) and (2) respectively [38,39].
Where “r” and “H” are the radius and height of the base of the tower respectively rb. and Lb are the radius of down conductor and the length of the blade. The Modeling of the tower and blade could be more detailed as those provided in [1–4,10–13], however these research works were intending to study the potential rise in the grounding system and the impact upon the body of the tower. Therefore, the detailed modeling for them was justified, unlike this paper where the main focus is the transmitted overvoltage to the electrical network and hence, the usage of approximated modeling justified as earlier used in [38,39].
Grounding resistance of the tower.
The modeling of the grounding resistance of the tower during lighting strikes requires the consideration of its value during transient response of the strike. The event of the lightning strike injects excessive amount of energy into the ground which ionizes it and changes its value. This variation of the resistance could be represented as a non-linear resistance (Rg) as given in (3) and (4) [40,41]. A mathematically controlled non-linear resistance model was implemented on ATP/EMTP using non-linear TACSRES component.
(3)
(4)
where Rgo, Rg, are the values of the grounding resistances of the tower during normal operating conditions and lightning strikes respectively, “I, Io” are the currents flowing into the grounding resistance and the minimal current value required for the soil to ionize respectively with calculation of Io given in (4). ρs and Eo are frequency dependent soil resistivity and the gradient of soil ionization respectively. The values of Eo, ρs and Rgo were used as 400 kV/m, 1000 Ω.m and 10 Ω respectively according to [41].
Generator of the wind turbine.
A 690 V synchronous generator model was used with leakage reactance of 0.1 H [37]. The body of the nacelle and the generator form a stray capacitance between them that has a value of few nano-farads and was set to 10 nF in this study [38,39]. The inclusion of this capacitance in the model is very important as it allows the simulation of the inducted overvoltage into the electrical system of tower from the lightning surge propagating through the tower body.
Transmission lines, feeders and cables. Transmission lines were modeled using frequency-dependent line models such that the parameters used followed the data given in Table 1 [37]. Similar approach was used for cables with consideration of their lengths as previously described in system under study section.
Power transformers.
Transformers were modeled using frequency-dependent transformer component upon ATP. The modeling of the stray capacitance between each winding and the ground between the windings with each other was implemented by using capacitive elements connected across transformer [19,37].
Lightning strike.
Lightning strikes was modeled as an impulse surge current source that is injected to the location of the strike. The formulation of lightning surge according to Heidler function is given in (5) and (6) [26,33].
Where Io is the peak value of lightning impulse; τ1 and τ2 are the rise and tail times of the impulse respectively, n is the exponent factor and η is the peak value correction factor. The values of the parameters of the lightning impulse depend on its type. Two types are studied in this work; positive, and negative according to their standard parametric data as follows:
Simulation results
The system described in system under study section was modeled as stated in modeling of the system section and lightning strikes were created to hit the blades of the wind turbines. To consider the range of possibilities of the lightning induced overvoltages, two extreme cases were chosen for the defining the turbine selected to be hit by lightning. These cases include the hit location to be at the blades of first the tower closest to the grid or the one farthest to the grid. For each case, considerations of single, double and triple blade hit by lightning strikes were taken during the testing process. The results focused on the overvoltages propagating from blade to tower and then to the 220 kV/22 V transformer connected to the grid will be examined. That to evaluate the amount of damage that will reach the wind farm and the grid. The previous sequence was repeated for different wind turbine topologies to allow a comparison between the results of these cases and define the impact of changing the wind farm topology upon the results.
Radial topology
The first step is defining, the strike locations which will be W1 as the closest turbine to the grid and W13 as the farthest one. For each of them, single positive and negative strikes will be applied at first. Then double-blade and triple blade hit by positive and negative strikes will be tested for both turbines. The peak values for positive strikes are relatively larger than negative therefore for positive strikes peaks of 200, 150 and 100 kA are considered while for negative 100, 75, 50 kA are considered [10]. The peak values of strikes hitting double blades and were considered equal, while in triple-blade were considered unequal as in lightning branching scenario. In such way of peak selection, a consideration for different peak scenarios is simulated. The parameters of the tested cases are defined in Table 2 with cases given numbers from R-1 to R-12 such that initial letter R stands for radial. The overvoltage induced at each cases upon the blade tip, the top of the tower, the generator within the turbine and the 22 kV bus of the 220/22 kV transformer are recorded in Table 2. The maximum overvoltage at the low voltage bus of the grid transformer for case R-5 to R-12 are shown in Fig 3.
Overvoltages at low-voltage bus of the grid connected transformer in radial topology for cases (a) R-5 (b) R-6 (c) R-7 (d) R-8 (e) R-9 (f) R-10 (g) R-11 (h) R-12.
From the results shown in Table 2, several features could be defined for lightning induced overvoltage reaching the grid side from radial topology:
- F1. The induced overvoltages reaching the transformer connected to the grid are higher for negative strikes than positive strikes.
- F2. The highest magnitude of the injected overvoltage reaching the grid transformer are from lightning strikes the farthest tower from the grid for positive strikes and the opposite for negative strikes.
- F3. Double blade and triple blade hits generally increase the induced overvoltage reaching the transformer connected to the grid, and when compared to the single strike overvoltage of the same case it is found a percentage of increase from 20% up to 94%.
The previous features are further analyzed and discussed in analysis and discussion section. The same testing procedures are applied for remaining topologies in this section to if these features apply also to them or not, and more importantly to compare the variance in results between these topologies.
Single sided ring topology
The testing procedures were re-done for the SSR topology. The parameters of the tested cases are given in Table 3 with cases notated as SSR-1 to SSR-12. The maximum overvoltage at the low voltage bus of the grid transformer for case SSR-5 to SSR-12 are shown in Fig 4. The results show that the features previously defined for radial topology also applies for SSR-topology. For feature F3, the double and triple blade hits allowed an increase in overvoltage in range of 23.3% as in Phase A of SSR-5 to 97.8% as in phase C of SSR-12 when compared to single strikes of the same parameters. The comparison between cases of radial and their counter parts in SSR topology shows a general reduction in the induced overvoltage. The reduction percentage ranged from 11.75% for phase A from SSR-4 when compared to R-4, to 50.78% for phase C of SSR-5 when compared to R-5. Hence, a new feature is added to those mentioned in radial topology subsection as follows:
- F4. Induced lightning overvoltage reaching the transformer connecting to the grid are generally reduced in SSR topology than radial topology by range from 11.75% to 50.78%.
Overvoltages at low-voltage bus of the grid connected transformer in SSR topology for cases (a) SSR-5 (b) SSR-6 (c) SSR-7 (d) SSR-8 (e) SSR-9 (f) SSR-10 (g) SSR-11 (h) SSR-12.
Double sided ring topology
Testing cases for DSR topology were re-made in the same sequence as previous topologies. The parameters of tested cases are given in Table 4 for cases DSR-1 to DSR-12. The results show the DSR topology follows the same features previously introduced in other topologies. Also, feature F3 had the same pattern such that the double and triple blade hits allowed a 22.5% to 95.2% increase in overvoltage when compared to single strikes of the same parameters for phase B of DSR-8 and phase C of DSR-11 respectively. For the last feature introduced in SSR topology where the overvoltages were reduced in it, the DSR also furtherly reduces the overvoltages to be lower than SSR and radial topologies. The percentage of reduction of the maximum overvoltage with respect overvoltages recorded for radial topologies in the same cases were in range of 49.7% for phase A in DSR-11 to 66.7% for phase A in DSR-12.
Star topology
The testing cases for this topology following the same parameters as presented in Table 5. The notation of the cases within this topology will be initiated with letter S from S-1 to S-12. The recorded overvoltage at the low voltage side of the grid connected transformer for cases S5 to S12 are shown in Fig 5. The results of the table confirm the applicability of features F1 to F4 on the star topology. In regards of feature F3, the double and triple blade hits allowed a 16.8% to 103.1% increase in overvoltage when compared to single strikes of the same parameters for phase A of S-5 and phase C of S-11 respectively. The star topology shows the minimal injected overvoltage in comparison to SSR, DSR and radial topologies. The percentage of reduction ranged from 66.7% for phase A in case S-8 to 89.04% for phase C in case S-3. It could be concluded that the star topology has the highest ability to reduce overvoltage with respect to radial topology thus allowing the injected overvoltage reaching the grid to be minimal.
Overvoltages at low-voltage bus of the grid connected transformer in star topology for cases (a) S-5 (b) S-6 (c) S-7 (d) S-8 (e) S-9 (f) S-10 (g) S-11 (h)S-12.
Analysis and discussion
The variance between the responses of the topologies to lightning strikes could be articulated within the features previously defined in simulation results section. The degree of variance in some features and the peculiar characteristics found in some features are analyzed in this section.
- F1: it is observed in this feature that the injected overvoltages into the grid from negative lightning strikes are higher from positive strikes even for positive strikes for higher peaks. This is explainable on the bases of the fundamental laws of electromagnetic induction. As the lightning surge is transmitted to generator of the wind turbine through electromagnetic induction between nacelle body and the generator of the turbine. The most effective element of induction is the rate of change of the associated magnetic flux, which is much higher in negative strikes that much lower rise and tail times.
- F2: positive strikes hitting the farthest turbine overvoltage injects higher overvoltage to the grid than closer ones. This could be explained for radial topology of Fig 1A and generalized for other topologies. As the strikes hits the farthest turbine, the injected overvoltages propagates on a path towards the grid. The path depends on the impedance of the cables which are equal allowing maximum transfer of the travelling wave. The connected transformer for the turbines on that path absorb negligible amount of the surge for their lower impedance during positive strikes which could be considered to have lower frequency than negative strikes. On the other hand, when the positive strike hits turbine closest to the grid, at the first turbine the surge is diverted between two paths, one towards the farm and the other towards grid. The division allows a significant reduction in injected overvoltages to grid in case of hitting the closest turbines than hitting the farthest turbine.
For negative strikes, the feature is reversed where closest turbine injects higher overvoltages than farthest turbines. The same explanation used in previous paragraph could be re-used with one main fundamental difference, which is the impedance of transformers connected to the turbines. As in negative strikes, the frequency dependent impedance of these transformers will be much higher for negative strikes that have much smaller rise times than for positive strikes. So, when negative strikes hit the farthest turbine and as surge propagates towards the grid, a high potion of the travelling wave will be absorbed by higher impedance transformers. Thus the surge reaches the grid will be much smaller than for positive strikes. Hence, in negative strikes this feature is opposite to positive strikes. - F3: This feature could be summarized that hitting multi-blade either double-blade and triple blade had increased the injected overvoltage for all topologies in the following manner. The increase was in range of 20% up to 94%, 23.3% to 97.8%, 22.5% to 95.2% and 16.8% to 103.1% for radial, SSR, DSR and star topologies respectively. Generally, it could be concluded that for all topologies there is an expected increase of 15% to 100% in the injected overvoltage to the grid when the lightning strikes multi-blades.
- F4: The final feature shows that the star topology had the least injected overvoltage to the grid. This is attributed to its star connection allowing the deviation of injected overvoltage among the highest number of paths and reducing the injected overvoltage through the grid path. The percentage of reduction for the injected overvoltages with respect to radial topology, reached 50.78%, 66.07% and 89.04% for SSR, DSR and star topology respectively. It confirms that the star topology had the highest percentage of reduction in overvoltage compared to radial topology.
The previous comparison could be summarized in a single table as presented in Table 6.
Conclusion
The topological impact of wind farms upon the injected overvoltage from lightning strikes for possible single and multi-blade strikes were examined in this paper. The data from a real system were used to simulate a testing environment for various possible cases in the simulation process using ATP software. Four main topologies were considered; radial. SSR, DSR and star topologies. Different types of lightning were included either positive or negative strikes with a consideration for a multi-blade hit scenario. The features of the injected overvoltage to the grid were recorded in each topology. These features were used to define the point of similarities and the range of variances between these topologies. The main features could be summarized as follows:
- F1. Negative lightning strikes inject higher overvoltage to the grid due to their higher rate of change in comparison to positive lightning strikes. The higher rate of change of negative lightning strikes increases the rate of change of the associated magnetic flux which is reflected in the induced surge which propagates through the wind farm.
- F2. Strikes at the farthest turbine from the grid injects higher overvoltage than strikes to the closest turbine for positive strikes. This was found to be due to the flow path of flow of the surges which depends on the impedance value during the strikes. The opposite is applicable for negative strikes. The reason for the difference between positive and negative strikes in this feature is the frequency dependent impedance of the transformers which has much higher value in negative strikes than positive strikes. That difference in impedance would affect the value of surge reaching the gird.
- F3. Lightning strikes hits to multi-blades was found to increase the injected overvoltage for all topologies in range of 15% to 100% with respect to the overvoltage generated by lightning strikes hitting single blade.
- F4. The star topology had the least injected overvoltage to the grid. The reason behind that is the nature of the star otology which has several parallel path. The propagating surge of overvoltage that gets divided among these paths which results in a significant reduction in their value. Hence the highest reduction of overvoltage value was found in star topology as 89.04%. The percentage of reduction for the injected overvoltages reached 50.78%, 66.07% and 89.04% for SSR, DSR and star topology respectively and all with respect to radial topology.
It is finally recommended to consider star topology for wind farms to minimize any possible injected lightning overvoltage into the grid.
References
- 1. Feng J, Shen WZ. Design optimization of offshore wind farms with multiple types of wind turbines. Applied energy. 2017 Nov 1;205:1283–97.
- 2. Costoya X, DeCastro M, Carvalho D, Feng Z, Gómez-Gesteira M. Climate change impacts on the future offshore wind energy resource in China. Renewable Energy. 2021 Sep 1;175:731–47. Q. Sun, L. Yang, Z. Zheng, J. Han, Y. Wang, and L. Yao. "A comprehensive lightning surge analysis in offshore wind farm." Electric Power Systems Research 211 (2022): 108259.
- 3. Jung C, Schindler D, Laible J. National and global wind resource assessment under six wind turbine installation scenarios. Energy conversion and management. 2018 Jan 15;156:403–15.
- 4. Hosseini SA, Mohammadirad A, Akmal AA. Surge analysis on wind farm considering lightning strike to multi-blade. Renewable Energy. 2022 Mar 1;186:312–26.
- 5. Venkatesh PM, Babu AR, Suresh K. Experimental investigations on modified savonius wind turbine with curtain arrangements in the middle of the highway. European Journal of Electrical Engineering. 2018;20(3):267.
- 6. VijayBabu IA, Rajyalakshmi V, Suresh K. Renewable Energy Integrated High Gain DC-DC Converter with Multilevel Inverter for Water Pumping Applications. Journal of Advanced Research in Dynamical and Control Systems. 2017;9(1):172–90.
- 7. Luo F L, "Design of wind-turbine energy system," 2010 Conference Proceedings IPEC, Singapore, 2010, pp. 110–115.
- 8. Charabi Y, Abdul-Wahab S. Wind turbine performance analysis for energy cost minimization. Renewables: Wind, Water, and Solar. 2020 Aug 17;7(1):5.
- 9. Narasipuram RP, Mopidevi S. A Dual Primary Side FB DC-DC Converter with Variable Frequency Phase Shift Control Strategy for On/Off Board EV Charging Applications. In2023 9th IEEE India International Conference on Power Electronics (IICPE) 2023 Nov 28 (pp. 1–5). IEEE.
- 10. Glushakow B. Effective lightning protection for wind turbine generators. IEEE Transactions on Energy Conversion. 2007 Feb 20;22(1):214–22.
- 11. Rodrigues RB, Mendes VM, Catalão JP. Protection of interconnected wind turbines against lightning effects: Overvoltages and electromagnetic transients study. Renewable energy. 2012 Oct 1;46:232–40.
- 12. Radičević BM, Savić MS. Experimental research on the influence of wind turbine blade rotation on the characteristics of atmospheric discharges. IEEE Transactions on Energy Conversion. 2011 Sep 15;26(4):1181–90.
- 13. Zhang X, Zhang Y, Xiao X. An improved approach for modeling lightning transients of wind turbines. International Journal of Electrical Power & Energy Systems. 2018 Oct 1;101:429–38.
- 14. Shariatinasab R, Kermani B, Gholinezhad J. Transient modeling of the wind farms in order to analysis the lightning related overvoltages. Renewable energy. 2019 Mar 1;132:1151–66.
- 15. Tao S, Zhang X, Wang Y, Yang J. Transient behavior analysis of offshore wind turbines during lightning strike to multi-blade. IEEE Access. 2018 Apr 17;6:22070–83.
- 16. Malcolm N, Aggarwal R. The significance of median natural lightning current strokes on the energy handling capabilities of surge arresters employed in wind farms. Renewable energy. 2016 Jan 1;85:319–26.
- 17. Li X, Wang J, Wang Y, Fan Y, Zhang B, Wang S, Zhou M, Cai L. Lightning transient characteristics of cable power collection system in wind power plants. IET renewable power generation. 2015 Nov;9(8):1025–32.
- 18. Abouelatta MA, Ezzat M, Abd-Allah MA, Said A. Analysis and mitigation of the lightning overvoltage in capacitively coupling grid connected offshore wind turbine. International Journal on Electrical Engineering and Informatics. 2022 Jun 1;14(2):443–64.
- 19. Tao S, Yao X, Liu B, Zhang X, Wang Y. Research of lightning transient potential on the jacket foundation offshore wind turbines. InE3S Web of Conferences 2019 (Vol. 95, p. 02006). EDP Sciences.
- 20. Zalhaf AS, Abdel‐Salam M, Mansour DE, Ookawara S, Ahmed M. Assessment of wind turbine transient overvoltages when struck by lightning: experimental and analytical study. IET Renewable Power Generation. 2019 Jun;13(8):1360–8.
- 21. Zhang X, Zhang Y, Liu C. A complete model of wind turbines for lightning transient analysis. Journal of Renewable and Sustainable Energy. 2014 Jan 1;6(1).
- 22. Zhang L, Lao H, Wang G, Zou L, Zhao T, Fang Z. A new method for spatial allocation of turbines in a wind farm based on lightning protection efficiency. Wind Energy. 2019 Oct;22(10):1310–23.
- 23. Deshagoni RG, Auditore T, Rayudu R, Moore CP. Factors determining the effectiveness of a wind turbine generator lightning protection system. IEEE Transactions on Industry Applications. 2019 Jul 29;55(6):6585–92.
- 24. Alipio R, Conceição D, De Conti A, Yamamoto K, Dias RN, Visacro S. A comprehensive analysis of the effect of frequency-dependent soil electrical parameters on the lightning response of wind-turbine grounding systems. Electric Power Systems Research. 2019 Oct 1;175:105927.
- 25. Mohammed Z, Hizam H, Gomes C. Lightning-induced transient effects in a hybrid PV–wind system and mitigation strategies. Electric Power Systems Research. 2019 Sep 1;174:105882.
- 26. Abd_Elhady AM, Sabiha , r MA. Overvoltage investigation of wind farm under lightning strokes. In IET Conference on Renewable Power Generation (RPG 2011) 2011 Sep 6 (pp. 1–6). IET.
- 27. Yasuda Y, Hara T, Funabashi T. Analysis of lightning surge propagation in wind farm. Electrical Engineering in Japan. 2008 Jan 30;162(2):30–8.
- 28. Wadie F. Evaluative analysis for standardized protection criteria against single and multiple lightning strikes in hybrid PV-wind energy systems. Electric Power Systems Research. 2023 May 1;218:109227.
- 29. Rodrigues RB, Mendes VM, Catalão JP. Analysis of transient phenomena due to a direct lightning strike on a wind energy system. Energies. 2012 Jul 17;5(7):2545–58.
- 30. McGowan JG, Rogers AL. Wind energy explained: theory, design and application. John Wiley & Sons; 2010.
- 31. Eliyan T, Taha IB, Wadie F. Comparative assessment of switching overvoltages suppression measures in different wind farm topologies. IEEE Access. 2023 Jun 13.
- 32. Wadie F. Investigative analysis of the impact of the climatic induced pollution upon the insulators in 500 kV HVDC transmission line. Electric Power Systems Research. 2023 Jul 1;220:109244.
- 33. Bian X, Wu Y, Zhou Q, Jiang R, Zhang Y, Chen L, Qi Q, Lyu W. Simulation of cloud-to-ground lightning strikes to wind turbines considering polarity effect based on an improved stochastic lightning model. Atmosphere. 2023 Jan 3;14(1):108.
- 34. Pineda N, Montanyà J, Salvador A, van der Velde OA, López JA. Thunderstorm characteristics favouring downward and upward lightning to wind turbines. Atmospheric research. 2018 Dec 1;214:46–63.
- 35. Vidyadhar P, Cotton I. Lightning Protection of Wind Turbines–A Comparison of Real Lightning Strike Data and Finite Element Lightning Attachment Analysis. In 2009 International Conference on Sustainable Power Generation and Supply, pp. 1–8. IEEE.
- 36. Elshahed M, Ragab A, Gilany M, Sayed M. Investigation of switching over-voltages with different wind farm topologies. Ain Shams Engineering Journal. 2021 Sep 1;12(3):2695–707.
- 37. Stipetic N, Filipovic-Grcic B, Uglešic I, Tokic A. Investigation of direct lightning strikes to wind turbine blades. InInternational Conference on Power System Transients (IPST), Perpignan, France 2019 Jun.
- 38. Jiang A, Fu Z, He Y, Wei B, Wang L. Surge analysis of onshore wind farm due to multiple lightning strokes. In2014 International Conference on Lightning Protection (ICLP) 2014 Oct 11 (pp. 1122–1127). IEEE.
- 39. Said A, Abd-Allah MA, Mohsen M. Alleviation of the transients induced in large photovoltaic power plants by direct lightning stroke. Ain Shams Engineering Journal. 2023 Apr 1;14(3):101880.
- 40. Zalhaf AS, Zhao E, Han Y, Yang P, Almaliki AH, Aly RM. Evaluation of the transient overvoltages of HVDC transmission lines caused by lightning strikes. Energies. 2022 Feb 16;15(4):1452.
- 41. IEC T. 61400–24 “Wind turbine generator systems–Part 24: Lightning protection”. IEC: Switzerland. 2002;7.
- 42. IEC 61643–11: “Low-voltage surge protective devices—Part 11: Surge protective devices connected to low-voltage power systems -Requirements and test methods”; 2011.