Figures
Abstract
A new virtual synchronous generator (VSG) control strategy was researched and proposed for a VSC-HVDC (High Voltage Direct Current Based on Voltage Source Converter) transmission system. It can be applied to half-bridge or full-half-bridge hybrid topology modular multi-level converter (MMC) to improve the stability and reliability of the system. First, it is proposed that the energy stored in the equivalent capacitor of MMC power module was used to imitate the rotor inertial of synchronous generator. It can buffer transient power fluctuations and synchronize autonomously with the grid. Then the impedance characteristics of the proposed control method have been deduced and analyzed. The results show that the VSG control loop mainly improves the low frequency characteristics of the converter. Secondly, the ability to suppress transient fault current is weak. So, a method, that the given values of inner current loop are calculated by grid impedance matrix, was used. A double closed loop control structure composed by a power outer loop based on VSG control and a current inner loop is obtained. The simulation results show that it can effectively improve the current control capability during the transient process for systems with a 1:2 ratio of converter capacity to grid capacity (The grid short-circuit capacity is 60MW and the MMC is 30 MW). Finally, a hybrid MMC simulation model was built based on PSCAD and the steady-state and transient fault ride-through simulations were performed. The power adjustment time of MMC under the proposed VSG control is about 1s, while the adjustment time under the conventional control strategy is greater than 4s.
Citation: Wu J, Yin S, Li C, Zhang Q (2022) Inertial imitation method of MMC with hybrid topology for VSC-HVDC. PLoS ONE 17(12): e0277553. https://doi.org/10.1371/journal.pone.0277553
Editor: Yogendra Arya, J.C. Bose University of Science and Technology, YMCA, INDIA, INDIA
Received: February 28, 2022; Accepted: October 30, 2022; Published: December 9, 2022
Copyright: © 2022 Wu et al. This is an open access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.
Data Availability: All data are included in the paper.
Funding: This work was supported by National Natural Science Youth Foundation of China (Grant No. 11904233). The funders had an important role in decision to publish.
Competing interests: The authors have declared that no competing interests exist.
I. Introduction
Voltage source converter-based high voltage direct current transmission (VSC-HVDC) technology has emerged and developed rapidly in the past 30 years. It has been widely used in large-scale wind farms, photovoltaics and other renewable energy centralized access to the grid and asynchronous AC system interconnection. With the continuous improvement of the capacity and voltage level of the VSC-HVDC converter, the power system needs the converter to participate in the voltage and frequency regulation of the AC system. The traditional control strategy of the converter relies on the phase-locked loop (PLL) to be synchronized with the AC grid. When the AC system is weak or the new energy capacity is relatively high, this is likely to cause system oscillations. In this regard, it is necessary to change the synchronization mechanism between the converter and the grid. Control strategies that can run autonomously need to be adopted, such as virtual synchronous generator (VSG) control [1–3], droop control [4, 5], power synchronization control [6, 7], etc. This type of control strategy synchronizes with the AC system by adjusting the grid-connected power, and can operate stably under grid-connected and islanding conditions, so there is no need to switch control structures. It is one of the research hotspots in VSC-HVDC converter control.
The VSG control method was first proposed by Lauxthal University of Technology in Germany in 2007. By simulating the complete seventh-order mathematical model of the synchronous generator, it equivalently obtains the moment of inertia and damping characteristics of the synchronous generator. Since then, the application research of virtual synchronous generator technology in converter control has been carried out, various equivalent methods of generator inertia, and improved and optimized control strategies have been proposed, for example, a control method based on frequency deviation and frequency change rate adaptively changing inertial constant and damping coefficient [8, 9], improving the equivalent damping characteristic of the system by adding a feedforward control branch to the power control branch [10, 11], and droop control used as the outer control loop to dynamically adjust the VSG operating point, enhancing system oscillation suppression capability [12, 13],and so on.
More specifically, such as the literature [14, 15], the VSG control structure is applied to the outer control loop of the doubly fed induction generator (DFIG). Its current amplitude reference signal and synchronous angular velocity of grid are calculated by VSG outer loop. In [16], a small-signal model of wind power converter based on VSG control is established. A method for optimizing the impedance characteristics of wind turbine converters is proposed based on DC capacitors, which eliminates the risk of oscillation between wind turbines and the grid. In [17], based on the conventional VSG strategy of wind turbine converters, the functional relationship between the equivalent virtual moment of inertia of the converter and its output power is established. The wind turbine state estimation function is designed to determine the level at which the wind turbine converter participates in grid frequency regulation according to its own regulation capability. However, the conventional VSG strategy does not directly control the current, and it is necessary to combine the inner current loop to suppress the transient current. In [18], the active power-virtual torque droop control and the DC voltage-frequency droop control are designed respectively. It outputs the grid synchronization signal which is used for the traditional double closed-loop control (outer power loop and inner current loop) under the synchronous rotating coordinate. In [19], the outer active power control loop is designed according to the swing equation of generator. And the state feedback method is used to improve the inner current loop of the traditional double closed-loop vector control. Then the power and current control are connected in series to form a new double closed-loop control structure. It can adaptively adjust the control parameters of the outer loop according to the fluctuation of AC frequency and power, and improve the system stability under different working conditions. In [20, 21], the converter voltage reference signal is obtained based by VSG control. And the concept of virtual synchronous impedance is proposed. It is used to connect the outer and the inner control loop to calculate the reference value of the inner current loop. It is proved that the characteristic root of the system state equation is only determined by the synchronous virtual impedance parameter, which avoids the influence of the deviation of the actual impedance parameter on the control performance.
The above research results describe in detail the idea of VSG control and its specific implementation method. VSG control has many advantages such as large stability margin for grid-connected operation, providing frequency support, and stable operation under islanding and grid-connected conditions. However, most of the research results are designed for two-level converters. The MMC topology is more complex and has more degrees of freedom for control. For VSG control structure and inertial equivalent method, there is still room for optimization. For control structures, the modulation signal is directly output by the traditional VSG controller, without direct control of the AC current, and the fault ride-through capability is poor. Therefore, a suitable current inner loop can be constructed to improve the transient characteristics of the system. For inertial equivalent, the inertial energy in the aforementioned VSG method needs to be provided by an AC power grid, an energy storage system or a wind turbine, which requires an additional device or system to provide or consume the inertial energy. The power module capacitor of the MMC itself can be used to store energy and provide inertia. For these aspects, the main contributions of this paper include: proposing an inertial simulation method for MMC topology, designing the current inner loop to improve the transient performance, and analyzing the impedance characteristics of the converter under the proposed control strategy. The converter under the proposed control scheme can provide transient inertia for the AC system, improve the transient fault ride-through capability of the system, and provide an optimized control scheme for the weak AC system to connect to the large-capacity power electronic converter. Specifically, in the second part, the control strategy of hybrid MMC is introduced. Based on this, the method of using the energy storage in power module capacitor of the hybrid MMC itself to provide inertia for VSC-HVDC system is proposed in the third part. Then, according to the proposed virtual inertial control strategy, the impedance characteristics of the converter are derived and analyzed. A method of constructing the current inner loop is also proposed, which can be connected to the outer loop based on VSG control to improve the system’s transient current control capability. And simulation verification of the proposed methods is in section four.
II. Control mode of VSC-HVDC based on hybrid topology MMC
The VSC-HVDC system based on the full-half-bridge hybrid topology MMC can isolate permanent DC faults and pass through the transient ones. The full-bridge power module effectively improves the fault ride-through capability and the DC voltage adjustment range with less increase in converter losses. Its topology is shown in Fig 1, MMC is composed of 6 arms, all of which are composed of a certain proportion of half-bridge and full-bridge power modules mixed in series. HB is the half-bridge power module and FB is the full-bridge one. Usj (j = a, b, c) is three-phase AC voltage of grid side and Vj is for valve side. Ij is the three-phase AC current on the secondary side of the transformer. Vdc and Idc are the DC voltage and DC current of the converter, respectively. And L is the bridge arm reactance.
Assuming that each bridge arm is composed of Nh HB power modules and Nf FB ones, the ratio of Nf to Nh is usually greater than or equal to 50% [22, 23]. Only the FB power modules can output negative voltage, so its proportion affects the DC fault clearing ability and the reactive power output ability during transient zero dc voltage operation, etc. For hybrid topology MMC, there is usually a DC current control loop used to quickly clear DC faults and suppress short-circuit current rise. It is shown in Fig 2. Idcref and Id are the reference and feedback value of DC current respectively. Their errors are connected to the PI regulator, and the common mode component Vdc_com of the modulation signal is output. Then it is superimposed on the AC modulation signals of the 6 arms. That is, by directly changing the DC component of the bridge arm modulation signal to control the DC current to track a given value. During the transient DC fault process, the DC component of the modulation signal is set to 0 or a small negative number, which helps to clear the DC fault. The AC component of the modulation signal is generated by the current inner loop, where Idref and id are the active (d-axis) current given and feedback value. Iqref and iq are the reactive (q-axis) current reference and feedback value respectively. PI regulators are used for dq-axis current tracking control, and their outputs are superimposed with the dq-axis feedforward component Usd and Usq of the grid voltage and the current cross-decoupling, and output Ucd and Ucq, the dq-axis components of the AC modulation signals. The PLL is used is used to obtain the grid synchronization angular velocity ω, and the Ucd and Ucq are transformed into modulation signals Uj (j = a,b,c) of abc stationary frame. Then DC modulation signal plus and minus AC ones to get the upper and lower arm modulation signals Uju, Ujn (j = a, b, c), respectively. vc_avg and are the average value of all power module voltages in 6 arms and its given value. Different from the commonly used for VSC-HVDC system, the average voltage of power module capacitor instead of DC voltage is used as the control target of outer loop [22, 23]. This can maintain the AC and DC power balance during the zero DC voltage operation.
For islanding control mode, the converter supplies power to passive loads. And the three-phase AC modulation signal Uj1 (j = a,b,c) is directly calculated by the outer AC voltage amplitude loop. As shown in Fig 2, and vac are the reference and feedback value of the AC voltage amplitude respectively, and ω1 is the rated angular frequency. the “control mode” signal is used to switch between islanding and grid connecting operation modes. In the process of control mode switching, it is difficult to synchronize the switching of the control structure and the closing of the grid-side circuit breaker, so this switching method may cause a large grid-connected inrush current.
III. VSG control of hybrid topology MMC
A. VSG-based average arm voltage control
As in the previous section, in the island operation mode, constant AC voltage amplitude and constant frequency control structure was used. In the grid-connected mode, the control structure of the DC capacitor voltage outer loop cascaded inner current loop is adopted, and based on the PLL to maintain synchronization with the grid. It cannot operate stably in island mode. This creates a problem that the control structure switching needs to be synchronized with the changes of islanding and grid-connected operation mode. It is difficult to synchronize them, because the mechanical structure of the AC circuit breaker will cause the closing time to be uncertain. Besides when connected to a weak AC system, the PLL output may fluctuate greatly, and the system will be unstable during startup and disturbance. In the VSG control idea, the synchronization mechanism of the AC generator is simulated. The output power of the converter is adjusted to maintain synchronization with the AC system. It can operate stably in islanding and grid-connected modes, which can avoid the switching of control structure,
A VSG control structure suitable for MMC topology is proposed in this section. The energy storage of the MMC equivalent capacitor corresponds to the inertial energy of the generator rotor. The energy storage of the power module itself is used to provide transient inertial support for the AC system. This improves system stability. And the current inner loop is designed to improve the transient current control capability of the traditional VSG. The equivalent inertia of the MMC capacitor can be obtained by comparing with rotor swing equation of the generator shown in Eq (1).
In (1), J is the moment of inertia. Pm and Pe are mechanical power and electromagnetic power. D is the damping coefficient. ωm and ωg are mechanical angular frequency of the generator rotor and the grid-side voltage, respectively. According to the principle of energy equivalence, the equivalent capacitance Ceq of MMC is shown in Eq (2)
(2)
Where CSM is the capacitance of one power module, and N is the total number of full-bridge and half-bridge power modules in one arm. Considering that the capacitance of all power modules is the same, then vc = Vdc / N. The Ceq can be obtained as in Eq (3)
(3)
From the power balance relationship between the AC and DC sides of the converter, Eq (4) can be obtained.
(4)
vcΣ is the sum of all power module capacitor voltages. Contrast Eq (1) and Eq (4), MMC power module capacitor voltage corresponding to the angular frequency of the generator. That is, the change of vcΣ reflects the fluctuation of output power. In the steady state, the AC and DC power are balanced, and the capacitor voltage is unchanged. During the transient, the power module capacitor can buffer power fluctuations. Establish the relationship between vcΣand ω, and we can get the moment of inertia simulated by the capacitors. Here, make the linear relationship between vcΣ and the generator speed ω, such as ω = 1/k⋅vcΣ. Eq (5) can be obtained.
From Eq (5), J = Ceq·k2, the proportional coefficient k is determined by the allowable operating range of the MMC module voltage. The capacitance and voltage of the full-bridge and the half-bridge modules are the same, so their contribution to the inertia of the system is also the same. In order to facilitate the design of control parameters, the average value vc_avg of the MMC capacitor voltage is used instead of the total capacitor voltage vcΣ. The equivalent capacitance Ceq corresponds to J, and the droop relationship between power and angular frequency in Eq (1) corresponds to Eq (6)
(6)
In Eq (6), ωn and ωm are the angular frequency of grid and converter output voltage. There is a drooping relationship between ωm and vc_avg. Based on the above, the converter control structure is proposed as shown in Fig 3. kvc and kv are the drooping coefficients of the capacitor voltage outer loop and reactive power outer loop, respectively. The phase θ and amplitude Eref of modulation signal transformed by polar coordinates to obtain the dq axis component of the modulation signal Edref and Eqref. Then the modulation signal is calculated by the inner current loop, which is transformed from the synchronous rotating coordinate to the stationary coordinate system as in Fig 3.
The converter outputs active power to the AC grid as the positive direction. When the average value of the module voltage is less than the reference value, it indicates that the output power to the AC grid has increased. The power module capacitor energy storage is converted into transient power support of grid, and the capacitor voltage in the steady state will be slightly lower than the rated value. The phase difference between the AC voltage vector of the converter and the grid voltage vector will increase, stabilizing at the new operating point. After that, other converters connected in parallel on the DC bus will inject power into this station from the DC side, and the voltage of the sub-modules in this station gradually recovers, which can continuously provide greater inertial support power to the AC system, which is equivalent to increasing the system’s moment of inertia.
In Fig 3, droop control is also used for the reactive power control loop, which adjusts the AC output voltage of the converter according to the reactive power deviation between the reference and actual value. This is similar to the principle of reactive power control of generators. PI regulator is used for DC voltage control loop, and the output is the common mode component of the upper and lower arm modulation signals. When the average voltage of the power module capacitors deviates from the rated value, the DC bus voltage is kept constant by adjusting the number of modules with on-state in the upper and lower arms.
B. Current control and system impedance characteristics
From the main circuit in Fig 1 and Kirchhoff’s law, the AC side equation of the converter can be obtained as:
(7)
R is the equivalent resistance of the AC circuit. The DC side model of the converter is obtained as
(8)
Eq (7) and Eq (8) are the mathematical model of the main circuit of the MMC. Considering that the control of inner loop contains current dq-axis cross-decoupling links, the coupling of the dq-axis current in the main loop can be removed, and Eq (7)–(8) can be linearized as shown in Eq (9).
In the equation:
,
,
,
,
.
It is a two-input two-output linear system. The two inputs include the dq axis modulation signal
., and the phase of AC voltage vector of converter side, u2 = Δθ. The two outputs include the dq axis current of the converter,
a the average of the sub-module capacitor voltage Δvc_avg.
The state equations of the system control loop can be obtained from Fig 3. The active power control loop is as in Eq (10).
The reactive control loop is as in Eq (11).
PI regulators are used for inner AC voltage and current control loop. Linearize the control loop shown in Eq (12).
The system small signal transfer function structure is obtained from the main loop and control loop linearization Eqs (9) and (12) shown in the Fig 4.
In the figure, the reactive power small signal feedback (ΔQfbk) is shown as Eq (13).
Each element in the coefficient matrix can be obtained from the steady-state operating point of the system, as shown in Eq (14).
From the small signal transfer function structure of the system in Fig 4, the relationship between and
can be obtained as Eq (15), which can be used for the system impedance calculation.
In Eq (15), is related to the converter input variables u1 and u2, so the relationship between u1 and u2 is first derived from Fig 4. It is as Eq (16).
From Eq (12) and Eq (16)
(17)
where
,
.
Bringing Eq (17) into Eq (15), we can get the system impedance model under the proposed control strategy. Take the impedance zdd between Δud and Δid as an example, the impedance characteristic of zdd shown in Fig 5.
According to the theoretical derivation and impedance scanning results, it can be seen that the system has an inductive characteristic in the high frequency region (>300Hz), which is similar to the traditional double closed-loop control strategy. The proposed virtual inertia control method mainly affects the impedance of the system in the low-frequency region.
C. VSG control of active power
For the converter station with active power as the control target in VSC-HVDC system, the control loop of the common mode component of the modulation signal needs to be changed compared with the constant DC voltage control station. It is shown in Fig 6, where Pref and Pfbk are the reference and feedback value of active power respectively. The output of the active power regulator PI1 is the DC current reference Idc_ref, and Idc is the feedback. The output of the DC current regulator PI2 is the common mode component of the modulation signal. It changes the DC side transmission power of the converter by adjusting the DC output voltage, so that the active power can track the reference value. The voltage and reactive power control structure of the power module in this figure is the same as that in Fig 3.
For the above control strategies of the two ends, in Figs 3 and 6, it is droop control characteristic between Vc_avg and ω in the outer control loop, and the energy during the transient process is buffered by changing the capacitor voltage. The capacitors provide inertia. The common mode component of the modulated signal can be used to control the DC voltage and active power to track the reference signals.
For the constant power control converter, the conventional VSG control loop can also be used. As shown in Fig 7, a first-order inertial link between the P and θ is used for inertial imitation. It can be represented by the Eq (18).
In Eq (18), s is differential operator. Based on swing equation of synchronous machine, the grid synchronization angular frequency ω can be obtained. Pm and Pe are mechanical power and electromagnetic power. D is the damping coefficient. H is the inertia time constant. The inner current loop is the same as Fig 3. For the control structure of Fig 7, the inertial support energy needs to be supplied by the active power input from the DC side, not by the MMC capacitor energy storage. Therefore, it requires additional energy storage or power supply on the DC side. This is the main difference from the control structure of the outer VSG control loop proposed in this paper.
IV. Simulation and analysis
In order to verify the proposed VSG control strategy, a VSC-HVDC system based on full-half-bridge hybrid MMC is built based on PSCAD. One terminal takes the active power or AC voltage and frequency as the control target. The control structure is shown in Fig 6. The other one takes the DC voltage as the control target and the control structure is shown in Fig 3. The control parameters of the VSG outer loop are determined by the impedance characteristics of the small signal model, and the current inner loop controller parameters are mainly adjusted through simulation, so that the adjustment speed of the current inner loop is significantly higher than that of the outer loop. The conventional circulation suppression method is adopted for MMC station based on double-frequency rotating coordinate [24]. And The power module voltage sequencing method is used to maintain voltage balance during both steady state and transient state [25]. The main circuit structure is shown in Fig 8. The AC sides of the converters MMC1 and MMC2 at both ends are connected to the transformers T1 and T2 respectively. The equivalent inductance L1 and L2 of the grid is 5mH. The grid voltage Us1 and Us2 is 10 kV, so the short circuit capacity of the system is about 60 MW, MMC connected with weak AC system. The MMC1 can smoothly switch between islanding and grid-connected modes through circuit breakers CB1 and CB2. There are 10 power modules connected in series in one arm, including 5 half-bridge modules and 5 full-bridge ones. Power module rated voltage is 2kV and the DC voltage of VSC-HVDC system is 20 kV. Its rated power is 30 MW. The parameters in the simulation model are obtained by reducing the DC voltage level according to the VSC-HVDC project for reducing the amount of calculation [26], and keep the DC current at the same level.
System parameters are normalized with peaks of AC voltage and AC current in the simulation. Active and reactive power is normalized by system rated capacity. And adjusted by simulation, J = 0.0471 p.u., D = 1.1p.u. The AC side of MMC1 is connected to a passive load, with island control mode. The MMC2 is connected to the grid, and the DC voltage is controlled to the rated value. At t = 3s, the grid-connected operation signal is sent to MMC1, and the controller detects the phase difference between the output voltage of the MMC1 and the grid voltage. When the phase difference meets the requirements, the pre-synchronization process ends, and the grid-side circuit breaker CB1 is closed. The simulation results are shown in Fig 9. In island mode, the given frequency Fref is higher than the rated frequency of the grid, which is 1.01p.u. shown in Fig 9(A). Due to the deviation between Fref and the actual frequency of the power grid, the active power changes after the grid is connected. The P- ω link in Fig 3 quickly adjusts the angular frequency of the MMC output voltage to achieve self-synchronization with the power grid. the Pref and P in Fig 9(B) are the reference and feedback of the P- ω link, and its output is the angular frequency adjustment value Δω shown in Fig 9(C). this makes the MMC to track the grid frequency autonomously. As shown in the simulation results, although there is large static-state error during the grid connection process, the MMC can maintain synchronization with the power grid without switching the control structure, which can simplify the switching process and maintain the stable operation of the system. After the grid-connected process is over, conventional secondary regulation and other methods can be used to adjust the frequency reference signal to be the same as the actual frequency of the grid, and the active power will also track its reference.
In order to verify the transient power support performance of the proposed control method and the stability of access to the weak grid, at t = 4s active power steps change from 0MW to 30 MW. The simulation results are shown in Fig 10. The variable label "1" in the figure is the output waveform of the conventional double closed loop control method (Fig 2) for hybrid topology, and the label "2" is the output waveform based on VSG strategy.
Fig 10(A) and 10(B) are the waveforms of DC voltage and DC current, respectively. As shown in the figures, with conventional control strategy, there are large oscillations when the converter is unlocked and during the power step rising. The oscillation attenuation is slow, so the system characteristic is of weak damping. Fig 10(C) is the step response of active power. It can be seen from the control method shown in Fig 6 that the active power regulator will increase the common mode component of the modulation signal. This increases the on-state power modules, temporarily release the energy of the power module, and reduce the impact on the power grid. Then the average capacitor voltage control loop vc_avg−Δω adjusts the output angular frequency. That is, by adjusting the phase of the AC output voltage to increase the input active power. Fig 10(D) shows the PLL output ω1 of the conventional control strategy and the grid synchronization angular frequency ω2 calculated by the vc_avg−Δω control loop. It can be seen that the PLL output fluctuations during the unlocking and step response, indicating that if the weak AC system connected, the PLL characteristics deteriorate during the transient process, causing the system oscillation. Fig 10(E) shows the dq-axis current reference and feedback values during the step process based on VSG control strategy, and both d- and q-axis currents can track the given values during steady-state and step processes.
Hybrid topology MMC can suppress DC short-circuit current. For verification, DC bipolar short-circuit fault is set at t = 8s. The fault is cleared after 100 ms, and the simulation results are shown in Fig 11. And Fig 11(A) shows the DC voltage and current waveform during the DC fault. Fig 11(B) shows the dq-axis current reference and feedback, and there is a small fluctuation of feedback currents during the short-circuit process. Fig 11(C) also shows the dq-axis current reference and feedback based on reference [16] for comparison with the method in this paper. In [16], the VSG outer loop and the current inner loop structure are also used. But its inertial energy is provided by the wind turbine instead of the converter’s own capacitors. Although the wind turbine can provide greater inertial energy, in the process of transient DC fault, in order to keep the capacitor voltage constant, its current inner loop given value and feedback value fluctuate greatly, resulting in overcurrent blocking of the converter. Fault ride-through failure. In the method proposed in this paper, the VSG outer loop is constructed based on the capacitor energy storage of the power module. During the transient fault process, the given value of the power module voltage will be increased, which is the same as the change trend of the feedback value, thereby reducing the fluctuation of the current inner loop. Fig 11(D) shows the three-phase current (Ian, Ibn, Icn) of lower arms of the converter. During DC fault, the output of DC current control module rapidly reduces, which is the DC component of the modulation signals. This can make the DC voltage close to 0, suppress the DC short-circuit current from rising, and realize the transient DC fault clearing.
V. Conclusion
First of all, the control method of MMC can autonomously keep synchronous with the grid. It can solve the problem of strong coupling between the control structure and the main circuit operation mode in the traditional PLL-based control strategy, and simplify the switching process between islanding and grid connection of VSC-HVDC.
Secondly, based on the energy storage of MMC power modules, VSC-HVDC system can imitate synchronous generator characteristics. Capacitor average voltage of arms can be controlled by adjusting the angular frequency of voltage vector of converter side. It can buffer active power changes during transient process and improve system stability. When the converter valve is connected to the weak AC system, it can eliminate the system oscillation caused by the PLL during transient and effectively improve system stability.
Finally, through the analysis of the impedance characteristics of the VSG, it is shown that the outer loop of the VSG mainly affects the low-frequency characteristics of the system, and the high-frequency characteristics are still dominated by the current inner loop. The proposed control structure is of positive impedance at low frequency and can buffer the influence of the transient process on the AC system. In summary, the proposed VSG control technology applied to hybrid topology MMC can effectively improve the system stability and reliability of VSC-HVDC.
References
- 1. Yun Yang, Fei Mei, Chenyu Zhang. Coordinated adaptive control strategy of rotational inertia and damping coefficient for virtual synchronous generator [J]. Electric Power Automation Equipment, 2019, 9(3): 125–131.
- 2. Li Meiyi, Huang Wentao, Tai Nengling, et al. A Dual-Adaptivity Inertia Control Strategy for Virtual Synchronous Generator [J]. IEEE Transactions on Power Systems, IEEE Transactions on Power Systems, 2020, 35(1): 594–604.
- 3. Mandrile Fabio, Carpaneto Enrico, Bojoi Radu. VSG Simplified Damper Winding: Design Guidelines [J]. IECON 2019 - 45th Annual Conference of the IEEE Industrial Electronics Society, Lisbon, Portugal, IEEE, Oct. 2019: 14–17
- 4. Huaitian Zhang, Long Jing, Xuezhi Wu, et al. Control Strategy for Autonomous Operation of Power Electronic Transformer [J]. Automation of Electric Power Systems. 2018, 42(4): 89–94.
- 5. Sakamuri Jayachandra N., Ömer Göksu Ali Bidadfar, et al. Black Start by HVdc-connected Offshore Wind Power Plants [C]. 45th Annual Conference of the IEEE Industrial Electronics Society, Lisbon, IEEE, Oct. 2019: 7045–7050.
- 6. Zhang Lidong, Nee Hans-Peter, Harnefors Lennart. Analysis of Stability Limitations of a VSC-HVDC Link Using Power-Synchronization Control[J]. IEEE Transactions on Power Systems, 2011, 26(3): 1326–1337.
- 7. Harnefors Lennart, Hinkkanen Marko, Riaz Usama, et al. Robust Analytic Design of Power-Synchronization Control [J]. IEEE Transactions on Industrial Electronics, 2019, 66(8): 5810–5819.
- 8. Asrari Arash; Mustafa Mehran; Ansari Meisam, et al. Impedance Analysis of Virtual Synchronous Generator-Based Vector Controlled Converters for Weak AC Grid Integration [J]. IEEE Transactions on Sustainable Energy, 2019, 10(3): 1481–1490.
- 9. Sakimoto K, Miura Y, Ise T. Stabilization of a power system with a distributed generator by a virtual synchronous generator function[C]. Proceedings of the 8th International Conference on Power Electronics -ECCE Asia, Jeju, Korea, 2011: 1498–1505.
- 10. Yawei Wang, Bangyin Liu, Shanxu Duan, et al. Research on Transient Characteristic Optimization of Virtual Synchronization Generator Control Strategy [J]. Proceedings of the CSEE, 2019, 39(20): 5885–5893.
- 11. Bo Zhang, Xiaolei Zhang, Jiaoxin Jia, et al. Configuration Method for Energy Storage Unit of Virtual Synchronous Generator Based on Requirement of Inertia Support and Primary Frequency Regulation [J]. Automation of Electric Power Systems, 2019, 43(23):202–209.
- 12. Zuobin Zhu, Shaoping Huang, Zhenxing Li, et al. Research on Control Strategy for Micro-grid Adaptive Rotating Inertia Virtual Synchronous Generator [J]. Proceedings of the CSU-EPSA, 2020, 32(4): 111–115.
- 13. Li Dongdong, Zhu Qianwei, Lin Shunfu, et al. A Self-Adaptive Inertia and Damping Combination Control of VSG to Support Frequency Stability [J]. IEEE Transactions on Energy Conversion, 2017, 32(1): 397–398.
- 14. Zheng Deng, Guorong Liu, Zhenyuan Zhang, et al. Adaptive Control of Doubly-Fed Wind Turbines Based on Virtual Synchronizer [J]. Power System and Clean Energy, 2020, 36(8): 73–81.
- 15. Wang Shuo, Hu Jiabing, Yuan Xiaoming, et al. On Inertial Dynamics of Virtual-Synchronous-Controlled DFIG-Based Wind Turbines [J]. IEEE Transactions on Energy Conversion, 2015, 30(4): 1691–1702.
- 16. Yunyang Xu; Heng Nian; Bin Hu, et al. Impedance Modeling and Stability Analysis of VSG Controlled Type-IV Wind Turbine System [J]. IEEE Transactions on Energy Conversion, Early Access, 2021: 1–1.
- 17. Che Gao, Xinshou Tian, Yan Li, et al. Adaptive Virtual Synchronous Generator Control of DFIG Based on Operation State Evaluation [J]. Power System Technology, 2018, 42(2): 517–523.
- 18. Meng Xin, Liu Jinjun, Liu Zeng. A Generalized Droop Control for Grid-Supporting Inverter Based on Comparison Between Traditional Droop Control and Virtual Synchronous Generator Control[J]. IEEE Transactions on Power Electronics, 2019, 34(6): 5416–5438.
- 19. Yuntao Zou, Haitao Zhang, Chunyang Liu, et al. A Control Approach of Novel Virtual Synchronous Generator and An Adaptive Control Strategy for Its Transient Process [J]. Power System Technology, 2018, 42(03): 933–943.
- 20. Li Mingxuan, Wang Yue, Xu Ningyi, et al. A Novel Virtual Synchronous Generator Control Strategy Based on Improved Swing Equation Emulating and Power Decoupling Method[C]. 2016 IEEE Energy Conversion Congress and Exposition (ECCE), Milwaukee, WI, USA, 2016: 1–7.
- 21. Mingxuan Li, Yue Wang, Ningyi Xu, et al.Power Decoupling Strategy for Virtual Synchronous Generator Relaxing Condition of Small Power Angle [J]. Automation of Electric Power Systems. 2018, 42(09): 59–68
- 22. Weixing Lin, Jinyu Wen, Weizeng Liu. “Full Bridge Sub-Module Proportion Design and Non-Blocking Control of Overhead MMC-HVDC Transimssion System,” Southern Power System Technology, vol. 12, no. 2pp. 3–11 Nov. 2018.
- 23. Moke Feng, Yuqun Guo, Jianzhong Xu, et al. “Start-up Control Strategies of Hybrid MMC and Configuration of FBSM,” Journal of North China Electric Power University, vol. 44, no. 6 pp. 28–35 Nov. 2017.
- 24. Yang Zhen, Song Ping, Song Jian, et al. An MMC Circulating Current Suppressing Controller Based on Bridge Arm Common-Mode Voltage [J]. IEEE Access, Oct. 2020, vol.8, pp189471–189478.
- 25. Hu P. and Jiang D., “A level-increased nearest level modulation method for modular multilevel converters,” early access, IEEE Trans. Power Electron.,
- 26. Zou Changyue, Rao Hong, Xu Shukai, et al. Analysis of Resonance Between a VSC-HVDC Converter and the AC Grid [J]. IEEE Transactions on Power Electronics, 2018, 33, 12: 10157–10168.