The impact of heating, ventilation, and air conditioning design features on the transmission of viruses, including the 2019 novel coronavirus: A systematic review of ventilation and coronavirus

  • Gail M. Thornton,

    Roles Conceptualization, Data curation, Formal analysis, Investigation, Methodology, Project administration, Supervision, Validation, Visualization, Writing – original draft, Writing – review & editing

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Brian A. Fleck ,

    Roles Conceptualization, Data curation, Formal analysis, Funding acquisition, Investigation, Methodology, Project administration, Supervision, Validation, Visualization, Writing – original draft, Writing – review & editing

    brian.fleck@ualberta.ca

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Emily Kroeker,

    Roles Data curation, Formal analysis, Investigation, Visualization, Writing – original draft, Writing – review & editing

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Dhyey Dandnayak,

    Roles Data curation, Formal analysis, Investigation, Visualization, Writing – original draft, Writing – review & editing

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Natalie Fleck,

    Roles Data curation, Formal analysis, Investigation, Visualization, Writing – original draft, Writing – review & editing

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Lexuan Zhong,

    Roles Funding acquisition, Writing – review & editing

    Affiliation Faculty of Engineering, Department of Mechanical Engineering, University of Alberta, Edmonton, Canada

  • Lisa Hartling

    Roles Conceptualization, Data curation, Formal analysis, Funding acquisition, Investigation, Methodology, Project administration, Supervision, Writing – original draft, Writing – review & editing

    Affiliation Faculty of Medicine & Dentistry, Department of Pediatrics, University of Alberta, Edmonton, Canada

Abstract

Aerosol transmission has been a pathway for the spread of many viruses. Similarly, emerging evidence has determined aerosol transmission for Severe Acute Respiratory Syndrome coronavirus 2 (SARS-CoV-2) and the resulting COVID-19 pandemic to be significant. As such, data regarding the effect of Heating, Ventilation, and Air Conditioning (HVAC) features to control and mitigate virus transmission is essential. A systematic review was conducted to identify and comprehensively synthesize research examining the effectiveness of ventilation for mitigating transmission of coronaviruses. A comprehensive search was conducted in Ovid MEDLINE, Compendex, Web of Science Core to January 2021. Study selection, data extraction, and risk of bias assessments were performed by two authors. Evidence tables were developed and results were described narratively. Results from 32 relevant studies showed that: increased ventilation rate was associated with decreased transmission, transmission probability/risk, infection probability/risk, droplet persistence, virus concentration, and increased virus removal and virus particle removal efficiency; increased ventilation rate decreased risk at longer exposure times; some ventilation was better than no ventilation; airflow patterns affected transmission; ventilation feature (e.g., supply/exhaust, fans) placement influenced particle distribution. Few studies provided specific quantitative ventilation parameters suggesting a significant gap in current research. Adapting HVAC ventilation systems to mitigate virus transmission is not a one-solution-fits-all approach. Changing ventilation rate or using mixing ventilation is not always the only way to mitigate and control viruses. Practitioners need to consider occupancy, ventilation feature (supply/exhaust and fans) placement, and exposure time in conjunction with both ventilation rates and airflow patterns. Some recommendations based on quantitative data were made for specific scenarios (e.g., using air change rate of 9 h-1 for a hospital ward). Other recommendations included using or increasing ventilation, introducing fresh air, using maximum supply rates, avoiding poorly ventilated spaces, assessing fan placement and potentially increasing ventilation locations, and employing ventilation testing and air balancing checks.

Trial registration: PROSPERO 2020 CRD42020193968.

Introduction

On April 5, 2021, the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) declared that “Airborne transmission of SARS-CoV-2 is significant and should be controlled. Changes to building operations, including the operation of heating, ventilating, and air-conditioning systems, can reduce airborne exposures” [1]. This statement declaring that airborne transmission of Severe Acute Respiratory Syndrome coronavirus 2 (SARS-CoV-2) is “significant” replaced the April 2020 statement that airborne transmission of SARS-CoV-2 is “sufficiently likely”; however, both statements indicate that heating, ventilation, and air conditioning (HVAC) systems can influence airborne exposures. These ASHRAE statements represent an evolution in the understanding of coronavirus transmission since March 2020 [2] when the World Health Organization declared Coronavirus Disease 2019 (COVID-19), the disease caused by the SARS-CoV-2 [3], a pandemic.

International public health authorities have sought evidence regarding transmission routes and appropriate public health measures to mitigate virus spread since March 2020. Certain viruses are capable of aerosol transmission [4], which can occur when virus-laden aerosols are exhaled by humans and remain airborne for extended periods of time. Recent evidence suggests that SARS-CoV-2 can spread via airborne transmission, particularly in indoor environments with poor ventilation where the air inside is not exchanged with outdoor or fresh air enough to mitigate exposure risks, such as settings with low ventilation rates or areas with high concentrations of viruses or potentially infected air [5,6], further emphasizing the important role of HVAC in virus transmission. Appropriate measures for protecting occupants of indoor spaces based on informed, interdisciplinary research are critical to managing the spread of infectious disease [7].

While seven human coronaviruses have been identified, three have received the most attention because of their pathogenicity and lethality [8]: SARS-CoV-2, Severe Acute Respiratory Syndrome coronavirus (SARS-CoV), and Middle East Respiratory Syndrome coronavirus (MERS-CoV). Each of these coronaviruses had its first emergence in the last 18 years [8]: SARS-CoV in 2003, MERS-CoV in 2012 and SARS-CoV-2 in 2019. Coronavirus has emerged as an infectious agent of great concern for potential airborne transmission.

HVAC systems can reduce airborne virus exposure through dilution or removal of contaminated air inside the building envelope where humans breathe [7,911]. Virus transmission can be influenced by various HVAC design features, including ventilation, filtration, ultraviolet radiation, and humidity. Previous systematic reviews that examined HVAC systems and airborne transmission of infectious agents highlighted the need to quantify the HVAC parameters to minimize transmission. Li et al found sufficient evidence to demonstrate an association between transmission of infectious agents and ventilation rate and/or airflow pattern [9]. However, they found insufficient evidence to specify and quantify the minimum ventilation requirements in buildings in relation to the airborne transmission of infectious agents [9]. Similarly, Luongo et al demonstrated an association between increased infectious illness and decreased ventilation rate; however, insufficient data were found to quantify how mechanical ventilation may affect the airborne transmission of infectious agents [7]. Furthermore, a recent review by Shajahan et al reinforced the need to quantify the optimum range for HVAC parameters considering airborne exposure [12]. At this time, what remains unknown is the specific quantity of any particular HVAC design feature that is effective in reducing virus transmission.

The current systematic review examined whether virus transmission is affected by HVAC design features, particularly, ventilation. In this review, published research evaluating the effectiveness of ventilation in reducing coronavirus transmission was examined. The insight drawn from this review could help answer questions of the utility of ventilation to mitigate the transmission of SARS-CoV-2 in mechanically ventilated indoor environments. Further, understanding effectiveness relative to ventilation rate and airflow patterns could inform control measures.

Methods

As an integral part of a larger research program to identify and synthesize the scientific literature on airborne virus transmission and HVAC design features, this systematic review focused specifically on the impact of ventilation on coronavirus transmission. Owing to the volume and heterogeneity of the published research, results for the impact of other HVAC design features of interest on virus transmission are reported elsewhere. The a priori systematic review protocol is publicly available [13] and the systematic review is registered [14]. The review adheres to the standards for the conduct of systematic reviews defined by the international Cochrane organization [15] with modifications for questions related to etiology [16], and the accepted standards for reporting [17].

Search strategy

Using concepts for virus, transmission, and HVAC, a research librarian (GMT) searched three electronic databases (Ovid MEDLINE, Compendex, Web of Science Core) from inception to April 2020 with an update in January 2021. Search strategies were peer reviewed by two librarians (TL, AH) prior to implementing the searches. The search strategy for Ovid MEDLINE is provided in Table 1. Screening of reference lists of all relevant papers as well as relevant review articles was undertaken. Conference abstracts, identified through Compendex and Web of Science, were not included but searches were conducted to identify whether any potentially relevant conference abstracts had been published as peer-reviewed journal articles. Year and language limitations were not applied to the search; however, due to the volume of available literature and resource constraints, only English language studies were included. EndNote was utilized to manage records and duplicate records were removed prior to screening.

thumbnail
Table 1. Search strategy for Ovid MEDLINE ALL 1946 to Present13.

https://doi.org/10.1371/journal.pgph.0000552.t001

Study selection

Study selection was completed in two stages. First, the titles and abstracts of all references identified by the electronic databases searches were screened by two reviewers independently. Each record was classified based on relevance as Yes, Maybe, or No. One reviewer resolved conflicts between Yes/Maybe and No. After each round of pilot testing using three sets of studies (n = 199 each), the review team met to discuss discrepancies and develop decision rules. Second, the full text articles were reviewed and the inclusion and exclusion criteria were applied by two reviewers independently. Each study was classified as Include or Exclude. Consensus of the reviewers resolved conflicts between Include and Exclude. One reviewer resolved conflicts between different exclusion reasons. After each round of pilot testing with three sets of studies (n = 30 each), the review team met to resolve discrepancies. Study selection was conducted using Covidence software.

Inclusion and exclusion criteria

The inclusion and exclusion criteria are provided in Table 2. Given that this systematic review was part of a larger research program to examine virus transmission and different HVAC design features, searching and screening for all HVAC design features was conducted at once; however, only studies evaluating ventilation were synthesized in this paper. Likewise, searching and screening considered a variety of agents (e.g., bacteria, fungi) but prioritized studies of viruses or agents that simulated viruses. For this specific review, the synthesis was further narrowed from viruses to coronaviruses. Studies of the indoor built environment (e.g., office, public, residential buildings) with mechanical ventilation were of interest. Primary research with quantitative results of correlation or association between ventilation and coronavirus transmission was included. English-language, peer-reviewed publications were included with no limitation on year of publication.

thumbnail
Table 2. Inclusion and exclusion criteria for systematic review [13].

https://doi.org/10.1371/journal.pgph.0000552.t002

Risk of bias assessment

Different risk of bias assessments tools were used for experimental and modelling studies. Risk of bias for experimental studies considered three domains: selection bias, information bias and confounding [18,19]. Each domain was assessed as low, high, or unclear risk of bias using signaling questions [20] from guidance documents for the different study types, e.g., animal studies, laboratory experiments, epidemiological studies [18,19,21]. Risk of bias for modelling studies considered three domains: definition, assumption, and validation [21,22]. Definition evaluated model complexity and data sources, assumption evaluated the description and explanation of model assumptions, and validation evaluated model validation and sensitivity analysis [22]. Each domain was assessed as low, high, or unclear risk of bias using signaling questions [2123]. After pilot testing among three review authors, the risk of bias was assessed by three reviewers (EK, DD, NF) independently and discrepancies were resolved by the review team.

Data extraction

General information was extracted regarding the study (authors, year of publication, country of corresponding author, study design) and methods (setting, population [as applicable], agent studied, intervention set-up). Details on ventilation parameters were extracted, including ventilation rate and airflow pattern. Ventilation rate may be expressed as air changes per hour (ACH), ventilation flow rates (m3/h, m3/min, L/min), ventilation usage (ventilation versus no ventilation), or as determined by carbon dioxide (CO2) levels (ppm). Quantitative data were extracted as well as results of relevant tests of statistical significance related to ventilation. The primary outcome of interest was quantitative measures of the association between ventilation and coronavirus transmission. Data were extracted on actual coronavirus transmission where available (i.e., infections), as well as virus removal, virus concentrations, particle dispersion, and particle persistence, probability of transmission and transmission risk (referred to as transmission probability/risk) and infection risk, infection transmission probability, infection probability, probability of infection, individual risk, and infection index (referred to as infection probability/risk) as applicable. Information regarding ventilation feature placement, supply/exhaust ratios, occupancy, filtration usage (as provided), and air balancing was also extracted. Employing a data extraction form spreadsheet to ensure comprehensiveness and consistency, one reviewer extracted data and a second reviewer verified data for accuracy and completeness. Discrepancies were discussed by the review team.

Data synthesis

Due to heterogeneity across studies in terms of study design, ventilation features examined, outcomes assessed, and results reported, meta-analysis was not possible as anticipated. Evidence tables describing the studies and their results were developed. Narrative synthesis of the results of relevant studies was provided alongside evidence tables describing the studies and their results. To facilitate meaningful synthesis and comparison across studies, studies were separated into three groups: ventilation use, airflow pattern, and ventilation rate and airflow pattern.

Results

12,177 unique citations were screened, where 2,428 were identified as potentially relevant from the title and abstract screening and 568 met the inclusion criteria (Fig 1). Of the 568, 332 were relevant to ventilation. Of the 332 relevant to ventilation, 217 were relevant to viruses and, of those, 32 were relevant to coronaviruses. Two of these relevant studies were related and are considered as one in the following syntheses [24,25]. Attempts were made to divide studies into tables examining ventilation rate or airflow pattern. Most studies examining both ventilation rate and airflow pattern were challenging to separate into either individual category and a third table was created: combined effect of ventilation rate and airflow pattern. However, the study by Shao et al could be separated into individual categories and appears in the ventilation rate table and the airflow pattern table [26]. Thus, 20 investigated ventilation rate, eight investigated airflow patterns, and five investigated the combined effect of ventilation rate and airflow patterns. Studies were published between 2004 and 2021 (median year 2020). While the SARS-CoV-2 studies were concentrated between 2020 and 2021, the MERS studies were in 2017 and 2020, and the SARS-CoV studies ranged from 2004 to 2020. Most studies were conducted in the United States (n = 11) and China (n = 10). Studies were funded by national research funding organizations (n = 15), university and state grants (n = 9), industries (n = 2), and public foundations (n = 2); nine studies did not report funding sources and two studies reported no external funding.

thumbnail
Fig 1. Flow of studies through the selection process (note: Search was conducted for all HVAC design features but only studies of ventilation and coronavirus are included in this manuscript).

https://doi.org/10.1371/journal.pgph.0000552.g001

Ventilation rate

Twenty studies, including modelling (n = 16), experimental (n = 3), and observational (n = 1) studies, analyzed the effect of ventilation rate on SARS-CoV-2/COVID-19 (n = 16),SARS-CoV/SARS (n = 3), and MERS-CoV (n = 2) (Table 3). Scenarios in the studies represented a variety of settings, including hospitals [2733], schools [27,34], dental clinics [35], office spaces [31,34,3638], laboratories [36], transport vehicles and hubs [34,3840], spaces used for singing [41], nail salons [42], conference and meeting rooms [32,38], experimental test set-ups [43], gyms [32,38], restaurants and nightclubs [32,38], elevators [26,38], and rooms, in both single [33,37,38,44,45] and multi-room facilities [45].

thumbnail
Table 3. Characteristics and results of studies examining ventilation rate and coronavirus transmission.

https://doi.org/10.1371/journal.pgph.0000552.t003

Of the 16 modelling studies analyzing ventilation rate, six studies found that increased ventilation (i.e., increased ACH) was associated with decreased transmission [27], virus concentration [31], probability of infection [36], infection risk [29,37], and risk of cross infection [44]. Two modelling studies found that increased ACH increased the efficiency of particle and virus removal [26,28]. Shao et al also found that increasing ventilation by using increased ventilation settings (i.e., more ventilation sites) was effective in particle removal [26]. Additionally, four modelling studies found that increasing ventilation rate (m3/h and m3/min) was associated with decreased infection probability [34,39], risk of airborne transmission [42], and infection index ƞ [33]. Sun et al also found that reduced occupancy was associated with lower minimum ventilation requirements [39]. Kennedy et al, when comparing no ventilation scenarios to ventilation scenarios, found that increased ventilation rate, through the use of ventilation systems, was associated with decreased infection risk [45]. Similarly, Miller et al, although not using a specified metric, determined that increased ventilation rate, which led to a subsequent decrease in viral aerosol loss rates, was associated with decreased probability of infection [41].

Two modelling studies used CO2 levels as an indicator of ventilation rate. Both studies found that increased ventilation rate was associated with decreased CO2 levels and, as a result, decreased infection transmission probability [35] and transmission [27]. Two other modelling studies explored the impact of ventilation rate on individual risk and exposure times [32,34]. Both found that increasing ventilation rate (measured as ACH or m3/h) was associated with longer exposure times before the individual risk exceeded acceptable risk levels [32] or the infection probability increased to 1% [34].

Of the 20 ventilation rate studies, four were experimental or observational studies. Like the modelling study by Kennedy et al [45], two studies found that increasing ventilation rate through the usage of ventilation (ventilation versus no ventilation) was associated with decreased airborne respiratory droplet persistence [30] and decreased individual infection risk [40]. Similar to other modelling studies using ACH [2629,31,32,36,37,44], Somsen et al found that increased ventilation rates above ~1–4 ACH were associated with decreased transmission risk [38]. One study examined the impact of ventilation rate with UV radiation: Qiao et al found that increasing ventilation rate (flow rate) was associated with lower log reduction and removal efficiencies of viable virus in combination with UV radiation [43]. A more detailed description of the role and influence of UV in virus mitigation was explored in a complementary UV radiation and virus transmission systematic review, resulting from this investigation into HVAC features and the impact on virus transmission [13].

While five ventilation rate studies provided recommendations, only two studies provided quantitative recommendations [28,36]. Yu et al suggested that an air change rate of 9 h-1, in a six-bed hospital ward, could potentially decrease elapsed particle removal time, resulting in decreased inhalation risk, while maximizing energy efficiency [28]. Augenbraun et al suggested ACH rates and associated wait times for individuals prior to work or equipment usage in office and laboratory settings [28]. In a typical 200 ft2 (18.58 m2) office room and a volume of 80,000 liters without filtration and ~2 fresh air changes (FCH), they recommended individuals wait six air changes or approximately 2.5 hours before reoccupying the office space [28]. Similar recommendations were made for a laboratory room without filtration: in a 500 ft2 (46.45 m2) laboratory room with a volume of 200,000 liters and High-Efficiency Particulate Absorbing (HEPA) or highly rated Minimum Efficiency Reporting Values (MERV) filtration, they recommended waiting one air change before reoccupying the laboratory room with different users [28]. Recommendations without quantitative metrics included avoiding poorly ventilated spaces [30], ensuring ventilation is operational before occupants enter rooms [44]. Other recommendations suggest increasing ventilation [40], introducing fresh air [40], and using maximum supply rates [44].

Airflow pattern

Seven studies, including modelling (n = 4), epidemiological (n = 2), and experimental and modelling (n = 1) studies, examined the impact of airflow pattern on SARS-CoV-2/COVID-19 (n = 6) and SARS-CoV/SARS (n = 1) (Table 4). Settings included airplane cabins [46], restaurants [24,25,47], hospitals and healthcare facilities [4850], supermarkets [26], and classrooms [26].

thumbnail
Table 4. Characteristics and results of studies examining airflow pattern and coronavirus transmission.

https://doi.org/10.1371/journal.pgph.0000552.t004

Two of the four modelling studies determined that the placement of ventilation grilles was important in the dispersion of infectious particles [26,48]. Shao et al showed that when the supply and exhaust grilles were near the infectious particle emitter, the infectious particles were less dispersed [26]. You et al found the infection risk in an airliner cabin to be lower when displacement ventilation was used compared to mixing ventilation [46]. Miller et al determined that viral particles shed in patient rooms of an experimental negative pressure isolation space could spread from room to room or leak into the hallway when the patient room doors are open [49]. Further, viral particles shed in the hallway could infiltrate into patient rooms.

Miller et al examined the dispersion of viral particles in the experimental negative pressure isolation space and found, following the use of careful protective measures, that, as of June 23, 2020, no facility-acquired transmission of SARS-CoV-2 was identified [49]. Ding et al found that airflow leakage from isolation rooms to the corridor of the fifth floor of a hospital (similar to the modelling results from Miller et al [49]) led to one weakly positive air sample of SARS-CoV-2 out of five samples taken from the corridor (a total of 46 air samples were taken from the hospital) [50]. Two studies that retroactively analyzed separate COVID-19 outbreaks in restaurants found that airflow pattern was an essential factor in the transmission of the virus [24,25,47].

Only one study provided quantified recommendations [49]; four studies provided recommendations without quantification [2426,47,48]. Miller et al recommended using a pressure difference between -2 and -25 Pa in negative pressure isolation spaces [49]. Other recommendations regarding airflow patterns included: increasing air changes and outdoor air usage while decreasing air recirculation [48]; improving ventilation generally [24,25]; assessing fan placement in relation to restaurant seating and ensuring frequent ventilation or applying ventilation systems [47]; and optimizing ventilation through increased ventilation locations [26].

Ventilation rate and airflow pattern

Five modelling studies analyzed the effect of both ventilation rate and airflow patterns on SARS-CoV-2/COVID-19 (n = 1), SARS-CoV/SARS (n = 3), and MERS-CoV (n = 1) (Table 5). These modelling studies used settings representing hospital wards [5154], three of which were the Prince of Wales Hospital in Hong Kong [5153], and a supermarket [55].

thumbnail
Table 5. Characteristics and results of studies examining combined effect of ventilation rate and airflow pattern on coronavirus transmission.

https://doi.org/10.1371/journal.pgph.0000552.t005

Three studies analyzed the 2003 outbreak of SARS in ward 8A of the Prince of Wales Hospital, Hong Kong [5153]. Two studies agreed that airflow balancing reduced the concentration and dispersion of virus particles [51,52], although Li et al found that the impact was relatively small [51]. In addition, Li et al found that downward ventilation provided a greater reduction in the dispersion of the virus particles compared to mixing ventilation in the imbalanced airflow case [51]. Lim et al found that air supplied from the room boundary and exhausted in the center of the room provided a greater reduction in the dispersion of the virus particles compared to the inverse case in both balanced and imbalanced airflow cases [52]. In agreement with Li et al who found a small effect of airflow balancing on virus particle concentration and dispersion [51], Chen et al determined that airflow balancing had a relatively small to no effect on the dispersion of virus particles in the hospital ward, which was simulated using multi-zone modelling [53].

Satheesan et al found that increasing the ventilation rate greatly reduced the infection risk for patients situated farther away from the corridor within the ward [54]. However, increasing the ventilation rate also resulted in an increase of the infection risk of corridor users and its connected amenities. Installing exhaust grilles close to each patient reduced infection risk within the ward as well as the corridor. Vuorinen et al found that increasing exhaust flow rates and decreasing air mixing was the most effective intervention to reduce infectious particle concentrations [55].

Two studies analyzing both ventilation rate and airflow patterns provided recommendations [51,55]. Recommendations included designing ventilation systems so that cross-infection was minimized, with regular ventilation testing and air balancing checks [51]. Additionally, Satheesan et al recommended exhaust placement near patients, ideally above the head of the patient [54].

Risk of bias

Twenty of the 23 modelling studies had low risk of bias for all three domains: definition, assumption, validation. Two modelling studies had low risk of bias for assumption and validation but had unclear risk of bias for definition as there was a lack of clarity regarding contribution of fresh air in Augenbraun et al [36], as noted in the differences between Table 2 and Fig 1, and regarding the HEPA filter efficiency in Kennedy et al [45]. All eight experimental studies had low risk of bias for all three domains: selection bias, information bias, confounding (for the comparison of interest to this review).

Discussion

A review of 32 ventilation and coronavirus studies offered several crucial observations. First, increased ventilation, whether through ventilation rates (ACH, m3/h, m3/min, L/min) or as determined by CO2 levels (ppm), was associated with decreased transmission, transmission probability/risk, infection probability/risk, droplet persistence, and virus concentration, and increased virus removal and efficiency of virus particle removal. Second, increased ventilation rate was associated with decreased risk for longer exposure times. Third, the use of ventilation was associated with better outcomes than no ventilation scenarios. Fourth, airflow patterns were associated with transmission cases. Fifth, HVAC ventilation feature (supply/exhaust or fans) placement was associated with varied particle distribution. As well, changing ventilation rate or using mixing ventilation is not always the only way to mitigate viruses. Finally, while some studies provided recommendations, few provided specific quantification of ventilation parameters suggesting a significant gap in current research.

Increasing the ventilation rate is an obvious solution to decreasing the risk of viral infection [2730,33,34,3739,4042,44,54]. However, there are some caveats. Adhikari et al found that increasing the ventilation rate did not affect the close-range airborne transmission route [29]. This means that an infected person may transmit the virus to close contacts regardless of the ventilation rate. Increasing the ventilation rate can also lead to wider spread of the virus, sometimes outside of the ventilated space, as suggested by Satheesan et al [54] and Borro et al [33]. This is why the airflow pattern can play a key role in transmission of the virus.

Airflow pattern in a room is governed by the location of diffusers and exhausts and the volume of air supplied and exhausted. The airflow pattern influences the distribution of the airborne virus in the space. Improper ventilation design can help spread viral particles to larger spaces beyond the proximity of the infected individuals. It can also create local hotspots relative to the infected individual [26]. Li et al [51] and Lim et al [52] both found that unbalanced or improperly balanced ventilation could increase the spread of airborne viral particles outside of the index patient’s room. However, by manipulating the HVAC system, spread of the virus particles outside of the room can be prevented [48]. Shao et al determined that multiple supply diffusers at a specified ventilation capacity can significantly improve the viral particles removal rate compared to a single diffuser at the same ventilation capacity [26]. Lim et al found that a balanced supply of air at the boundary and exhausting it in the middle of the room prevents the spread of airborne viral particles [52]. The strategic placement and airflow rate of exhaust grilles can be a crucial factor in designing for infection mitigation [54]. Lu et al attributed an outbreak of SARS-CoV-2 in a restaurant located in Guangzhou to the weak exhaust system which led to the continued presence of viral particles in the air [24,25]. In a restaurant located in Jeonju, Korea, Kwon et al found that only visitors in the airflow path were infected with SARS-CoV-2 [47]. Additionally, it only took 6.5 seconds for the viral particles to travel from the infector to the infectee. To combat this, Augenbraun et al suggests situating individuals in different airstreams so each individual is in their own occupied region which minimizes air mixing [36]. You et al [46] and Vuorinen et al [55] agree that mixing ventilation might not be the most suitable from the perspective of infection mitigation and that other patterns such as displacement ventilation should be considered. Maintaining a certain airflow pattern can be challenging. Chen et al found that a temperature difference between two spaces can interrupt the intended airflow pattern and cause unintentional air exchange between two spaces [53]. They suggested that reducing the area of openings by installing curtains would be an effective approach for reducing virus transmission.

From our review of the literature, it is clear that enhancing the ventilation, whether through increasing the ventilation rate or modifying the airflow pattern, is an effective way to reduce airborne viral infection risk. It is recognized that enhancing ventilation across an entire building might not be feasible due to economic or HVAC system limitations. Buonanno et al suggests paying close attention to spaces where the occupants are engaged in high expiratory activities such as singing, speaking loudly, or heavy exercising [32]. If mechanical ventilation is not available or is insufficient, natural ventilation through opening windows and doors should be utilized. Harrichandra et al studied 12 nail salons in New York City and determined that the risk was lowest in the nail salon with the highest ventilation rate and that this nail salon did not have a dedicated exhaust and used natural ventilation [42]. However, natural ventilation would not be feasible in colder weather. Yu et al [28] and Miller et al [41] suggest pairing ventilation with high efficiency filtration and ultraviolet germicidal irradiation where possible. Irrespective of ventilation design, practices such as frequent handwashing [54], surface cleaning [54], and wearing masks [30,37,41,42,45] should not be overlooked.

Implications for research

Ventilation is an HVAC feature that incorporates and considers many factors such as ventilation rate, airflow patterns, and air balancing. Additionally, ventilation is affected by outside factors such as room size, airflow rates and volume, filtration usage, exhaust and supply ratios, and number of occupants, to name a few. As such, recommendations with quantified data can be hard to provide. As Li et al noted in their review, insufficient evidence was found to specify and quantify the minimum ventilation requirements in buildings in relation to the airborne transmission of infectious agents [9]. Unfortunately, this remains a gap in the literature. Within this review, only three studies provided specific, quantified recommendations [28,36,49]. These included using an air change rate of 9 h-1 for a typical six-bed hospital ward to potentially decrease the inhalation risk of viral particles and maximize energy efficiency [28]; waiting one air change for filtrated environments to six air changes for non-filtrated environments before reoccupying a room previously occupied by a different person [36]; and maintaining a pressure difference between -2 and -25 Pa in negative pressure isolation spaces [49].

While 10 other studies provided recommendations, they were qualitative (rather than quantitative) [2426,30,40,44,4748,51,54]. Ventilation rate recommendations include avoiding poorly ventilated spaces [30]; checking to ensure ventilation was operational before allowing occupants to enter a space and using maximum supply rates [44]; increasing ventilation rates and introducing fresh air [40,48]; and decreasing air recirculation [48]. Air pattern recommendations included improving ventilation generally [24,25]; evaluating fan placement in relation to restaurant seating and ensuring frequent ventilation [47]; and optimizing ventilation by increasing ventilation locations [26]. Finally, recommendations that considered ventilation rate and airflow patterns included suggestions to design ventilation systems in a way that minimized cross-infection using regular ventilation testing and air balancing checks [51] and placing exhaust locations near patients, ideally above the head of the patient [54].

Dai et al provided what appears to be quantitative data regarding necessary ACH to bring the infection probability to specific percentages, but they do not refer these recommendations or even suggestions [34]. However, Dai et al showed the potential for more elaborate quantitative recommendations [34]. As such, the current lack of quantitative data shows a research gap within ventilation literature and a potential topic or consideration for future research.

Implications for practice

In practice, ventilation should be used, i.e., something is better than nothing [30,40,45]. The ventilation requirements of the HVAC system should consider the occupancy of the space [34,39] and the interplay between ventilation rate, exposure time, and infection risk [32,34,42]. While a variety of settings were addressed, a major portion of the studies (15 of 32) discussed hospitals and/or healthcare facilities. As such, it is important to keep in mind that the portion of studies discussing health care settings (in particular hospitals), with their associated relatively high indoor air quality (IAQ), is not representative of typical filtration and ACH in other identified high risk-of-transmission buildings of concern. Considering diminishing return on improving ACH, practical efforts should be directed at the most high-risk sites (low ACH, crowded, and high-risk occupants or activities).

Interestingly, mixing ventilation might not always be the best and other airflow patterns should be considered to lower virus transmission [46,51,55]. These three studies found that alternative airflow patterns were better at negating transmission than mixing ventilation. An important point in most ventilation pattern studies is that they generally require location and characterization of the source, which in practical situations is difficult to ascertain. The decrease in risk available as an outcome is an essential factor to know if innovation and ventilation design are headed in the direction of “smart ventilation” using continuous sensing of occupancy (or even temperature of room occupants) to create control strategies for air supply flow rate and direction. More knowledge of how airflow patterns alone affect risk could lead to systems with real-time feedback control on airflow pattern.

Strengths and limitations

This systematic review was prepared according to rigorous methods established by the international Cochrane organization [15], and adheres to comprehensive and transparent reporting standards [17]. We followed an a priori protocol which is publicly available [13] and we registered the review prior to its conduct [14]. All data collected during the systematic review are reported within the manuscript. We conducted an extensive search to identify all relevant studies; however, due to resource constraints we only included studies reported in English. Nevertheless, we identified and included a large number of relevant studies that were conducted across a wide range of geographic areas (e.g., USA, China, Taiwan, Netherlands, Switzerland, Finland, Italy, Spain, Australia, Romania, South Korea). We were unable to assess for publication bias as we did not conduct meta-analyses due to variation across studies in terms of design, ventilation features examined, outcomes assessed, and results reported. However, we searched the grey literature to identify conference abstracts and recent publications.

Conclusion

In 2007, Li et al found insufficient evidence to specify and quantify the minimum ventilation requirements in buildings in relation to the airborne transmission of infectious agents, despite finding sufficient evidence to demonstrate an association between transmission of infectious agents and ventilation rate and/or airflow pattern [9]. In the intervening time, the literature on coronaviruses and ventilation reinforces the association between transmission and ventilation rate and/or airflow pattern but reveals the limited progress towards providing quantitative recommendations. The recommendations with quantified data were using an air change rate of9 h-1 for a hospital ward; waiting six air changes or 2.5 hours before allowing different individuals into an unfiltered office with ~2 FCH and one air change for a high-efficiency MERV or HEPA filtered laboratory; and using a pressure difference between -2 and -25 Pa in negative pressure isolation spaces. Qualitative recommendations included using or increasing ventilation, and the introduction of fresh air, using maximum supply rates, avoiding poorly ventilated spaces, assessing fan placement and potentially increasing ventilation locations, and employing ventilation testing and air balancing checks.

Acknowledgments

We thank Tara Landry and Alison Henry for conducting the peer review of the search strategies. We thank Samuel Ducholke, Kristen Rumbold, Larry Zhong, and Stella Mathews for their involvement in screening studies for inclusion.

References

  1. 1. ASHRAE. ASHRAE epidemic task force releases updated airborne transmission guidance. 5 April 2021. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). https://www.ashrae.org/about/news/2021/ashrae-epidemic-task-force-releases-updated-airborne-transmission-guidance. Accessed April 22, 2021.
  2. 2. World Health Organization (WHO). WHO Director-General’s opening remarks at the media briefing on COVID-19–11 March 2020. https://www.who.int/director-general/speeches/detail/who-director-general-s-opening-remarks-at-the-media-briefing-on-covid-19—11-march-2020. Accessed April 4. 2021.
  3. 3. World Health Organization (WHO). Naming the coronavirus disease (COVID-19) and the virus that causes it. https://www.who.int/emergencies/diseases/novel-coronavirus-2019/technical-guidance/naming-the-coronavirus-disease-(covid-2019)-and-the-virus-that-causes-it. Accessed April 15, 2021.
  4. 4. Leung NHL. Transmissibility and transmission of respiratory viruses. Nat Rev Microbiol. 2021. pmid:33753932
  5. 5. Noorimotlagh Z, Jaafarzadeh N, Martinez SS, Mirzaee SA. A systematic review of possible airborne transmission of the COVID-19 virus (SARS-CoV-2) in the indoor air environment. Environ Res. 2021;193:110612. pmid:33309820
  6. 6. Rahimi NR, Fouladi-Fard R, Aali R, Shahryari A, Rezaali M, Ghafouri Y, et al. Bidirectional association between COVID-19 and the environment: a systematic review. Environ Res. 2021;194:110692. pmid:33385384
  7. 7. Luongo JC, Fennelly KP, Keen JA, Zhai ZJ, Jones BW, Miller SL. Role of mechanical ventilation in the airborne transmission of infectious agents in buildings. Indoor Air. 2016;26:666–678. pmid:26562748
  8. 8. Zhu Z, Lian X, Su X, Wu W, Marraro GA, Zeng Y. From SARS and MERS to COVID-19: a brief summary and comparison of severe acute respiratory infections caused by three highly pathogenic human coronaviruses. Resp Res. 2020;21(1). pmid:32854739
  9. 9. Li Y, Leung GM, Tang JW, Yang X, Chao CYH, Lin JZ, et al. Role of ventilation in airborne transmission of infectious agents in the build environment–a multidisciplinary systematic review. Indoor Air. 2007;17:2–18. pmid:17257148
  10. 10. Bing-Yuan , Zhang Y-H, Leung NHL, Cowling BJ, Yang Z-F. Role of viral bioaerosols in nosocomial infections and measures for prevention and control. J Aerosol Sci. 2018;117:200–211. pmid:32226118
  11. 11. Tang JW, Marr LC, Li Y, Dancer SJ. Covid-19 has redefined airborne transmission. BMJ. 2021;373:n913. pmid:33853842
  12. 12. Shajahan A, Culp CH, Williamson B. Effects of indoor environmental parameters related to building heating, ventilation, and air conditioning systems on patients’ medical outcomes: A review of scientific research on hospital buildings. Indoor Air. 29(2):161–176. pmid:30588679
  13. 13. Thornton GM, Fleck BA, Zhong L, Hartling L. The impact of heating, ventilation and air conditioning (HVAC) design features on the transmission of viruses, including the 2019 novel coronavirus (COVID-19): protocol for a systematic review and environmental scan. Open Science Framework. 2020. https://doi.org/10.17605/OSF.IO/Y62V7.
  14. 14. Thornton G, Zhong L, Fleck B, Hartling L. The impact of heating, ventilation and air conditioning (HVAC) design features on the transmission of viruses, including the 2019 novel coronavirus (COVID-19): a systematic review. PROSPERO. 08 July 2020. https://www.crd.york.ac.uk/prospero/display_record.php?ID=CRD42020193968 Accessed July 8, 2020.
  15. 15. Higgins JPT, Thomas J, Chandler J, Cumpston M, Li T, Page MJ, et al. Cochrane handbook for systematic reviews of interventions version 6.0. Updated July 2019. Cochrane. Available from www.training.cochrane.org/handbook.
  16. 16. Moola S, Munn Z, Sears K, et al. Conducting systematic reviews of association (etiology): The Joanna Briggs Institute’s approach. Int J Evid Based Healthc. 2015;13(3):163–169. pmid:26262566
  17. 17. Moher D, Liberati A, Tetzlaff J, Altman D G. Preferred reporting items for systematic reviews and meta-analyses: the PRISMA statement. BMJ. 2009;339:b2535. pmid:19622551
  18. 18. Williams-Nguyen J, Bueno I, Sargeant JM, Nault AJ, Singer RS. What is the evidence that point sources of anthropogenic effluent increase antibiotic resistance in the environment? Protocol for a systematic review. Anim Health Res Rev. 2016;17(1):9–15. pmid:27427189
  19. 19. Office of Health Assessment and Translation (OHAT), Division of the National Toxicology Program, National Institute of Environment Health Sciences. Handbook for conducting a literature-based health assessment using OHAT approach for systematic review and evidence integration. National Toxicology Program, US Department of Health and Human Services, 4 March 2019. https://ntp.niehs.nih.gov/ntp/ohat/pubs/handbookmarch2019_508.pdf Accessed November 28, 2020.
  20. 20. Higgins JPT, Thomas J, Chandler J, Cumpston M, Li T, Page MJ, et al (editors). Cochrane Handbook for Systematic Reviews of Interventions version 6.2. Updated February 2021. Cochrane. Available from www.training.cochrane.org/handbook.
  21. 21. Samuel GO, Hoffmann S, Wright RA, et al. Guidance on assessing the methodological and reporting quality of toxicologically relevant studies: A scoping review. Environ Int. 2016;92–93:630–646. pmid:27039952
  22. 22. Mateus ALP, Otete HE, Beck CR, Dolan GP, Nguyen-Van-Tam JS. Effectiveness of travel restrictions in the rapid containment of human influenza: a systematic review. Bull World Health Organ. 2014;92(12):868–880D. pmid:25552771
  23. 23. Organisation for Economic Co-operation and Development (OECD). Guidance Document on the Validation of (Quantitative) Structure-Activity Relationship [(Q)SAR] Models. OECD Series on Testing and Assessment No. 69, OECD Publishing, 3 September 2014. https://doi.org/10.1787/9789264085442-en Accessed January 4, 2021.
  24. 24. Lu J, Gu J, Li K, et al. COVID-19 outbreak associated with air conditioning in restaurant, Guangzhou, China, 2020. Emerg Infect Dis. 2020;26(7):1628–1631. pmid:32240078
  25. 25. Lu J, Yang Z. COVID-19 outbreak associated with air conditioning in restaurant, Guangzhou, China, 2020. Emerg Infect Dis. 2020;26(11):2790–2792. pmid:32917292
  26. 26. Shao S, Zhou D, He R, et al. Risk assessment of airborne transmission of COVID-19 by asymptomatic individuals under different practical settings. J Aerosol Sci. 2021;151:1–9. pmid:32968325
  27. 27. Liao C-M, Chang C-F, Liang H-M. A probabilistic transmission dynamic model to assess indoor airborne infection risks. Risk Anal. 2005;25(5):1097–1107. pmid:16297217
  28. 28. Yu HC, Mui KW, Wong LT, Chu HS. Ventilation of general hospital wards for mitigating infection risks of three kinds of viruses including Middle East respiratory syndrome coronavirus. Indoor Built Environ. 2017;26(4):514–527.
  29. 29. Adhikari U, Chabrelie A, Weir M, et al. A case study evaluating the risk of infection from Middle Eastern Respiratory Syndrome Coronavirus (MERS-CoV) in a hospital setting through bioaerosols. Risk Anal. 2019:39(12):2608–2624. pmid:31524301
  30. 30. Somsen GA, van Rijn C, Kooij S, Bem RA, Bonn D. Small droplet aerosols in poorly ventilated spaces and SARS-CoV-2 transmission. Lancet. 2020;8(7):658–659. pmid:32473123
  31. 31. Riediker M, Tsai D-H. Estimation of viral aerosol emissions from simulated individuals with asymptomatic to moderate coronavirus disease 2019. JAMA Netw Open. 2020;3(7):e2013807. pmid:32716517
  32. 32. Buonanno G, Stabile L, Morawska L. Estimation of airborne viral emission: Quanta emission rate of SARS-CoV-2 for infection risk assessment. Environ Int. 2020;141:1–8. pmid:32416374
  33. 33. Borro L, Mazzei L, Massimiliano R, Piscitelli P, Miani A, Secinaro A. The role of air conditioning in the diffusion of Sars-CoV-2 in indoor environments: A first computational fluid dynamic model, based on investigations performed at the Vatican State Children’s hospital. Environ Res. 2021;193:1–10. pmid:33068577
  34. 34. Dia H, Zhao B. Association of the infection probability of COVID-19 with ventilation rates in confined spaces. Build Simul. 2020;13:1321–1327. pmid:32837691
  35. 35. Zemouri C, Awad SF, Volgenant CMC, Crielaard W, Laheij AMGA, de Soet JJ. Modeling of the transmission of coronaviruses, measles virus, influenza virus, mycobacterium tuberculosis, and legionella pneumophila in dental clinics. J Dent Res. 2020;99(10):1192–1198. pmid:32614681
  36. 36. Augenbraun BL, Lasner ZD, Mitra D, et al. Assessment and mitigation of aerosol airborne SARS-CoV-2 transmission in laboratory and office environments. J Occup Environ Hyg. 2020;17(10):447–456. pmid:32960737
  37. 37. Zhang X, Wang J. Dose-response relation deduced for coronaviruses from COVID-19, SARS and MERS meta-analysis results and its application for infection risk assessment of aerosol transmission. Clin Infect Dis. 2020:1–15. pmid:33119733
  38. 38. Somsen GA, van Rijn CJM, Kooij S, Bem RA, Bonn D. Measurement of small droplet aerosol concentrations in public spaces using handheld particle counters. Phys Fluid. 2020;32:1–4. pmid:33362399
  39. 39. Sun C, Zhai Z(J). The efficacy of social distance and ventilation effectiveness in preventing COVID-19 transmission. Sustain Cities Soc. 2020;62:1–10. pmid:32834937
  40. 40. Moreno T, Pintó RM, Bosch A, et al. Tracing surface and airborne SARS-CoV-2 RNA inside public buses and subway trains. Environ Int. 2021;147:106326. pmid:33340987
  41. 41. Miller SL, Nazaroff WW, Jimenez JL, et al. Transmission of SARS-CoV-2 by inhalation of respiratory aerosol in the Skagit Valley Chorale superspreading event. Indoor Air. 2020;00:1–10. pmid:32979298
  42. 42. Harrichandra A, Ierardi AM, Pavilonis B. An estimation of airborne SARS-CoV-2 infection transmission risk in New York City nail salons. Toxicol Ind Health. 2020;36(9):634–643. pmid:33085569
  43. 43. Qiao Y, Yang M, Marabella AI, et al. Greater than 3‐Log reduction in viable coronavirus aerosol concentration in ducted Ultraviolet‐C (UV−C) systems. Environ Sci Technol. 2021;55(7):4174–4182. pmid:33263988
  44. 44. Melikov AK, Ai ZT, Markov DG. Intermittent occupancy combined with ventilation: An efficient strategy for the reduction of airborne transmission indoors. Sci Total Environ. 2020;744:1–7. pmid:32721678
  45. 45. Kennedy M, Lee SJ, Epstein M. Modeling aerosol transmission of SARS-CoV-2 in multi-room facility. J Loss Prev Process Ind. 2021;69:1–7. pmid:33173256
  46. 46. You R, Lin C-H, Wei D, Chen Q. Evaluating the commercial airliner cabin environment with different air distribution systems. Indoor Air. 2019;29:840–853. pmid:31172603
  47. 47. Kwon K-S, Park J-I, Park YJ, Jung D-M, Ryu K-W, Lee J-H. Evidence of long-distance droplet transmission of SARS-CoV-2 by direct air flow in a restaurant in Korea. Korean Med Sci. 2020;35(46):e415. pmid:33258335
  48. 48. Anghel L, Popovici C-G, Stătescu C, et al. Impact of HVAC-Systems on the dispersion of infectious aerosols in a cardiac intensive care unit. Int J Environ Res Public Health. 2020;17:1–17. pmid:32927583
  49. 49. Miller SL, Mukherjee D, Wilson J, Clements N, Steiner C. Implementing a negative pressure isolation space within a skilled nursing facility to control SARS-CoV-2 transmission. Am J Infect Control. 2020;000:1–9. pmid:33022331
  50. 50. Ding Z, Qian H, Xu B, et al. Toilets dominate environmental detection of severe acute respiratory syndrome coronavirus 2 in a hospital. Sci Total Environ. 2021;753:1–8. pmid:32891988
  51. 51. Li Y, Huang X, Yu ITS, Wong TW, Qian H. Role of air distribution in SARS transmission during the largest nosocomial outbreak in Hong Kong. Indoor Air. 2004;15:83–95. pmid:15737151
  52. 52. Lim T, Cho J, Kim BS. The influence of ward ventilation on hospital cross infection by varying the location of supply and exhaust diffuser using CFD. J Asian Archit Build Eng. 2010;9(1):259–266.
  53. 53. Chen C, Zhao B, Yang X, Li Y. Role of two-way airflow owing to temperature difference in severe acute respiratory syndrome transmission: revisiting the largest nosocomial severe acute respiratory syndrome outbreak in Hong Kong. J R Soc Interface. 2011;8:699–710. pmid:21068029
  54. 54. Satheesan MK, Mui KW, Wong LT. A numerical study of ventilation strategies for infection risk mitigation in general inpatient wards. Build Simul. 2020;13:887–896. pmid:32211123
  55. 55. Vuorinen V, Aarnio M, Alava M, et al. Modelling aerosol transport and virus exposure with numerical simulations in relation to SARS-CoV-2 transmission by inhalation indoors. Saf Sci. 2020;130:1–23. pmid:32834511